Download Print this page
Redlion DA Series Installation Manual

Redlion DA Series Installation Manual

Port sled

Advertisement

Quick Links

DA Serial Port Sled
Installation Guide
z Individually isolated serial ports
z Three product offerings:
- Two RS232 ports
- Two RS485/RS422 ports
- One RS232 port and one RS485/RS422 port
V
z Up to 5000
rms isolation
z Industrial rated for harsh environments
z Wide operating temperature range
z Simplified deployment architecture
z Field installable
PACKAGE CHECKLIST
This product package should contain the items listed below. If
any items are missing or damaged, contact Red Lion immediately.
- DA Serial Sled
- Installation Guide
SAFETY SUMMARY
All safety related regulations, local codes and instructions that
appear in this document or on equipment must be observed to
ensure personal safety and to prevent damage to either the
device or equipment connected to it.
Do not use these products to replace proper safety interlocking.
No software-based device (or any other solid-state device) should
ever be designed to be responsible for the maintenance of
personnel safety or consequential equipment not equipped with
safeguards. Red Lion disclaims any responsibility for damages,
either direct or consequential, that result from the use of this
equipment in a manner not specified.
CAUTION: Risk of Danger
Read complete instructions prior to installation and
operation of the unit.
ATTENTION : Risque de danger
Lire les instructions complètes avant l'installation et
l'utilisation de l'appareil.
ORDERING INFORMATION
DESCRIPTION
2x RS232 ports (RJ12 connectors)
2x RS485/RS422 ports (RJ45 connectors)
1x RS232 port, 1x RS485/RS422 port
(RJ12 and RJ45 connectors respectively)
Spaces in listed part numbers are shown to improve readability, do not
include when searching for or ordering these parts.
A listing of the entire family of products and accessories can be found at
www.redlion.net
PART NUMBER
DA S00 PN22 21IS 000
DA S00 PN24 42IS 000
DA S00 PN22 45IS 000
1
For use with DA50 and DA70 series covered in DEMKO 20 ATEX
2268X and IECEx UL 20.0007X certificates
SPECIFICATIONS
1. POWER REQUIREMENTS: Power is supplied by the DA host
controller.
Max Power: 1.5 W
2. INTERFACES:
Individually isolated RS232, RS485/RS422
RS232 ports accessed via an RJ12 jack
RS485/RS422 ports accessed via an RJ45 jack
3. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: -40 to 75 °C
Storage Temperature Range: -40 to 80 °C
Vibration to IEC 60068-2-6: Operational 5-500 Hz, 2 g
Shock to IEC 60068-2-27: Operational 15 g
Operating and Storage Humidity: 0 to 95% max. RH non-
condensing
Altitude: Up to 2000 meters
4. CERTIFICATIONS AND COMPLIANCES:
Refer to the controller manual for agency certifications.
CE Approved
EN 61326-1 Immunity to Industrial Locations
Emission CISPR 11 Class A
IEC/EN 61010-1
RoHS Compliant
5. INSTALLATION REQUIREMENTS: Sled must be installed
inside the unit case with the hardware provided. See
"Installing the DA Serial Sled" for more details
6. WEIGHT: 3.1 oz (88 g)
DASERIAL- B
Drawing No. LP1128
Revised 03/2020

Advertisement

loading
Need help?

Need help?

Do you have a question about the DA Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Redlion DA Series

  • Page 1 (RJ12 and RJ45 connectors respectively) Spaces in listed part numbers are shown to improve readability, do not include when searching for or ordering these parts. A listing of the entire family of products and accessories can be found at www.redlion.net...
  • Page 2 130K d’être endommagées. 8. Close the retaining latches to ensure the carriage is fully seated into the Controller case. 130K COMM Note: All Red Lion devices connect A to A and B to B. Refer to www.redlion.net for additional information.
  • Page 3 Name Pin # Name Pin # Name Pin # Name TxEN TxEN 1, 4 1, 4 Support: support.redlion.net COMM COMM 4, 1 4, 1 Website: www.redlion.net 2, 3 2, 3 Inside US: +1 (877) 432-9908 3, 2 3, 2 Outside US: +1 (717) 767-6511...
  • Page 4 “Statement of Warranty Periods” (available at www.redlion.net) current at the time of shipment of the Products (the “Warranty Period”). EXCEPT FOR THE ABOVE-STATED WARRANTY, COMPANY MAKES NO WARRANTY WHATSOEVER WITH RESPECT TO THE PRODUCTS, INCLUDING ANY (A) WARRANTY OF MERCHANTABILITY;...

This manual is also suitable for:

Da50 seriesDa70 seriesDa s00 pn22 21is 000Da s00 pn24 42is 000Da s00 pn22 45is 000