Chiller and Inverter Air/Water heat pumps with axial fans
Controller Manual
Model
SHP M ECO 006A
SHP M ECO 008A
SHP M ECO 010
SHP M ECO 010T
SHP M ECO 012
SHP M ECO 012T
Fonderie SIME S.p.A.
----------------------------------------------------------------------------------------------------------------------------------------------
This manual has been created for informative purpose. The company declines any responsibility for the results of any projecting or any installation based on the explanations and/or on the technical specifications provided
in this manual. It is besides forbidden the reproduction under any form of the texts of the figures contained in this manual. This manual is a translation from the official italian language version. For reasons of environmental
respect the Company will not provide the hard copy in the original language which could be directly requested or downloaded from the Company website at any time. In case of any dispute, the original languate manual
will be the trusted one. Even partial reproduction PROHIBITED © Copyright - SIME SpA
SHP M ECO 014
SHP M ECO 014T
SHP M ECO 016
SHP M ECO 016T
-------------------------------------------------------
EN
cod. 7500375 - R08

Advertisement

loading
Need help?

Need help?

Do you have a question about the SHP M ECO 008A and is the answer not in the manual?

Questions and answers

Summary of Contents for Sime SHP M ECO 008A

  • Page 1 Company will not provide the hard copy in the original language which could be directly requested or downloaded from the Company website at any time. In case of any dispute, the original languate manual will be the trusted one. Even partial reproduction PROHIBITED © Copyright - SIME SpA...
  • Page 2 SHP M ECO Heat pump air/water inverters with axial fans 10-2022 M.S. A.B. Parameter visibility alignment, insertion of GI module chapters 05-2022 E.G. A.B. Update sizes 006A, 008A, elimination of GI module chapters 12-2021 M.S. A.B. Elimination cap. 9.1 03-2021 A.B.
  • Page 3 SHP M ECO Heat pump air/water inverters with axial fans INDEX 1. HOW TO KEEP THE MANUAL ..................6 1.1 GRAPHIC SYMBOLS USED IN THE MANUAL ............6 2. PERMITTED USED ......................6 3. GENERAL SAFETY GUIDELINES ..................6 3.1 PERSONAL PROTECTIVE EQUIPMENT ..............6 3.2 WORKERS' HEALTH AND SAFETY ................
  • Page 4 SHP M ECO Heat pump air/water inverters with axial fans 10.2.3 INSUFFICIENT HEAT EXCHANGE IN A DHW SYSTEM ........18 10.3 REMOTE-CONTROLLED FUNCTIONS ..............18 10.3.1 ON/OFF ........................ 18 10.3.2 SUMMER/WINTER MODE CHANGE ..............19 10.3.3 DHW CALL FROM DIGITAL INPUT ..............19 10.4 SYSTEM WATER REMOTE PROBE ................19 10.5 AUXILIARY HEATERS ....................
  • Page 5 SHP M ECO Heat pump air/water inverters with axial fans 12.4.2 COLLECTOR PROTECTION .................. 29 12.4.3 COLLECTOR OVERTEMPERATURE ALARM ............29 12.4.4 DHW OVERTEMPERATURE ALARM ..............29 12.4.5 SOLAR EXHAUST VALVE ..................29 12.4.6 DISSIPATION OF SOLAR TANK HEAT ..............29 12.4.7 ANTIFREEZE ......................29 13.TABLES OF PERMITTED SETUPS FOR USER AND INSTALLER ........30 14.ALARMS ........................
  • Page 6: Graphic Symbols Used In The Manual

    SHP M ECO Heat pump air/water inverters with axial fans 1. HOW TO KEEP THE MANUAL The manual has to always be kept together with the unit it refers to. It has to be stored in a safe place, away from dust and moisture. It must be accessible to all users who shall consult it any time they are in doubt on how to operate the equipment.
  • Page 7 SHP M ECO Heat pump air/water inverters with axial fans IT IS PROHIBITED: To remove and/or to tamper with any safety device. For unauthorised personnel to access the electric panel. To work on live systems. To touch the systems if not authorised to do so To allow children or unassisted disabled persons to use the appliance.
  • Page 8: Purpose And Contents Of The Manual

    SHP M ECO Heat pump air/water inverters with axial fans The power supply has to respect the limits shown on the unit’s technical label: failing this, the warranty will terminate imme- diately. Before beginning any type of operation, make sure that power is disconnected. Connect the conductors in order: phase, neutral and earth.
  • Page 9: Setpoint Menu

    SHP M ECO Heat pump air/water inverters with axial fans 5. USER INTERFACE - CONTROLLER Select the operating mode and manually reset any alarms. Each time you press the key you have the following sequence: OFF -> COOL -> HEAT -> OFF If DHW is enabled, the sequence is the following: OFF ->...
  • Page 10 SHP M ECO Heat pump air/water inverters with axial fans SETPOINT DESCRIPTION UNIT DEFAULT RANGE **rHEA Mixing valve Winter setpoint °C 30.0 0.0 ÷ 80 (*) If the DHW function is enabled, see par. 10.2 (**) If Gi accessory is included, access is only possible with installer password. 5.3 PASSWORD MENU [PSS] Enter the password according to the desired access level.
  • Page 11 SHP M ECO Heat pump air/water inverters with axial fans IDENTIFICATION CODE OF THE DESCRIPTION PARAMETER INDEX VISIBILITY GROUP *Mixer valve i01- INSTALLER (*) To configure if Gi module present To access the installer parameters: PRG -> PSS -> PRG -> (enter Service password) ->PRG ->PAr -> PRG Please note that the menu is password-protected.
  • Page 12: Terminal Block

    SHP M ECO Heat pump air/water inverters with axial fans 5.12.1 LED Cooling mode LED • LED ON if unit is in cooling mode. Heating mode LED • LED ON if unit is in heating mode. Pump LED • LED ON if pump running. Alarm LED •...
  • Page 13 SHP M ECO Heat pump air/water inverters with axial fans Example of single phase unit terminal block X-1.1 X-22.1 X-20.1 X-19.1 X-17.1 X-15.1 X-16.1 X-5.1 X-14.1 X-11.1 X-10.1 X-9.1 X-6.1 X12-2 X12-1 X-22.2 X-20.2 X-19.2 X-17.2 X-15.2 X-16.2 X-5.2 X-4.1 X-14.2 X-11.2 X-10.2...
  • Page 14 SHP M ECO Heat pump air/water inverters with axial fans Setpoint Setpoint CURVE Heat Cool 20°C 25°C 20°C -29°C 40°C 10°C 20°C -28°C 40°C 15°C 20°C -25°C 5°C 5°C 37°C -17°C 10°C 8°C 40°C -20°C 6.2 EDIT THE SET-POINT FROM 0-10V INPUT OR FROM RATIOMETRIC INPUT Another type of adjustment allows you to edit the setpoint by adding (or subtracting) a value depending on the 0-10V input (if enabled).
  • Page 15 SHP M ECO Heat pump air/water inverters with axial fans • operating on call by temperature controller with periodic activation; • continuous operation (default); The circulator is switched off immediately if: • There is a manual reset pump block alarm, including the flow switch alarm; •...
  • Page 16 SHP M ECO Heat pump air/water inverters with axial fans Speed P06/P09 ΔT [°C] The circulator is at maximum speed in DHW production. Note: If the parameter r33 > 0, then the circulator can be running on call even to activate the system and/or sanitary heater, see par.10.8. 7.6 SYSTEM VENTING Function used to vent the system, with the circulator at maximum speed.
  • Page 17: Controller Functions

    SHP M ECO Heat pump air/water inverters with axial fans • b05 = compressor regulation delta cut-off = 0,2°C (default) • b25 = compressor regulation delta cut-on = 2°C Tw,out,set HzMaxReg HzMin Tw,out (outlet water temp.) ∆T,set + 2°C • The compressor shutdown is regulated by parameter b05: the compressor shutdown when is regulated by parameter b05 Tw,out > Tw,out,set + b05 •...
  • Page 18: Remote-Controlled Functions

    SHP M ECO Heat pump air/water inverters with axial fans Switching from utility water to domestic hot water, the working probe changes from “water outlet probe” to “DHW tank probe”. Switching from winter mode to sanitary mode, the compressor does not switch off and is brought to the maximum frequency established by the controller, whereas switching from summer mode to domestic hot water, the compressor is switched off and waits a safety time.
  • Page 19 SHP M ECO Heat pump air/water inverters with axial fans I/O resource - Parameter Value Function Closed contact -> active DHW call. ID9 can be activted via H53 Open contact -> inactive DHW call. The poles of the digital input can be swapped by setting H76=1 The SAN setpoint of the heat pump is not considered, the designer is in charge of managing this setpoint, taking into account domestic hot water protection and configuration of the entire system.
  • Page 20 SHP M ECO Heat pump air/water inverters with axial fans If domestic hot water production lasts longer than r16 (minutes) or if the machine blocks due to triggering of an alarm, the heater switches on. It switches off when the unit finishes domestic hot water production (also taking into account an offset on the setpoint with parameter r31, as explained in Paragraph 10.11.1).
  • Page 21 SHP M ECO Heat pump air/water inverters with axial fans Considering the operating modes in heating and/or DHW, there are 4 operating areas: Outside temp. Heat pump STANDARD WORKING Heat pump + Boiler/Heater JOINT OPERATION I ZONE Boiler + Heat pump/Heater JOINT OPERATION II ZONE Boiler/Heater OPERATION IN SUBSTITUTION...
  • Page 22 SHP M ECO Heat pump air/water inverters with axial fans of intervention of the integrations occurs in a certain operating mode of the unit; other statuses and values of the parameters can be selected instead and therefore they are provided in the same cell separated by the symbol ”/”). TABLE 1.
  • Page 23 SHP M ECO Heat pump air/water inverters with axial fans TABLE 2. JOINT OPERATION, BRACKET 1 INTERVENTION ORDER N° STATUS OPERATION (with setpoint not reached) 10 1) Heat pump HEAT / Set the min- HEAT+SAN HEAT/DHW 0/1/2 2) After r12 minutes, boiler utes minutes 1) Heat pump...
  • Page 24: Auxiliary Systems Offset Management

    SHP M ECO Heat pump air/water inverters with axial fans TABLE 4. OPERATION IN SUBSTITUTION INTERVENTION ORDER N° STATUS OPERATION (with setpoint not reached) 1) Plant/DHW integration heater HEAT / Set the min- Set the min- HEAT+SAN HEAT/DHW 0/1/2 2) After r12 minutes, boiler utes utes HEAT /...
  • Page 25: Double Set-Point

    SHP M ECO Heat pump air/water inverters with axial fans 10.11 WARNINGS If the double setpoint function is not active, one of the following warnings can be configured. 10.11.1 PLANT SEASON A digital output can be configured indicating the operating season of the unit, plant side. The output is active in summer mode, while it is deactivated in OFF or heating mode.
  • Page 26: Flow Meter

    SHP M ECO Heat pump air/water inverters with axial fans Parameter VALUE Function Function not active Enabling minimum Hz Function not active Function active only in cooling mode Function active only in heating mode Function active only in sanitary mode Function active in cooling and sanitary mode Function active in heating and sanitary mode Function active in cooling and heating mode...
  • Page 27 SHP M ECO Heat pump air/water inverters with axial fans • Climatic compensation; • Booster circulator management; • Management of single pump in a network; • Alarm diagnostic system. FUNCTIONS THAT CAN BE ACTIVATED WITH GI MODULE (OPTIONAL) The Gi module is an optional kit which allows you to manage the following functions: •...
  • Page 28 SHP M ECO Heat pump air/water inverters with axial fans 12.3 MIXER VALVE MANAGEMENT The mixer valve is regulated by means of specific PID which strives to maintain the delivery temperature of the radiant panel at the set value. The setpoint setting can be found in the 'Set' Menu: rCoo = Mixer flow temperature setpoint in cooling mode = 15°C (default) rHea = Mixer flow temperature setpoint in heating mode = 30°C (default The resources and the parameters to be setting are the following:...
  • Page 29 SHP M ECO Heat pump air/water inverters with axial fans • S06 = time OFF (default 15 seconds). As hysteresis to exit the protection condition use S08. This protection is guaranteed even with the machine Off. 12.4.3 Collector overtemperature alarm If the collector probe exceeds the value of parameter S12, there is an alarm condition E10 which blocks the solar circulator. The hysteresis to return from the alarm condition is given by parameter S08.
  • Page 30 SHP M ECO Heat pump air/water inverters with axial fans Allowed configurations: Parame- Description Unit Default Range Visibility Description Notes First cooling setpoint °C 25÷Coo2 First heating setpoint °C 45.0 Hea2÷H01 If sanitary function Sanitary setpoint °C 48.0 25÷H01 active. See par. 10.2 Coo2 Second cooling setpoint...
  • Page 31 SHP M ECO Heat pump air/water inverters with axial fans Allowed configurations: Parame- Description Unit Default Range Visibility Description Notes 0 = Output disabled Output configuration 0÷48 22 = Plant integration heater In DO3 power 26 = DHW integration heater Voltage output configuration 0 = Disabled output 0÷48...
  • Page 32 SHP M ECO Heat pump air/water inverters with axial fans Allowed configurations: Parame- Description Unit Default Range Visibility Description Notes Cooling temperature delta °C -10.0 -50.0÷80.0 Heating temperature delta °C 10.0 -50.0÷80.0 0-10V analogue input setting °C 0.0÷10.0 decalibration band 0-10V input 0-10V/ratiometric input en- 0÷1...
  • Page 33 SHP M ECO Heat pump air/water inverters with axial fans Allowed configurations: Parame- Description Unit Default Range Visibility Description Notes Do not modify this Joint operation bracket I up- value, as it could °C -16÷50 Respect r22 ≥ r28 ≥ r08 per limit jeopardise opera- tion of the unit...
  • Page 34 SHP M ECO Heat pump air/water inverters with axial fans Allowed configurations: Parame- Description Unit Default Range Visibility Description Notes Maximum solar DHW storage °C 0÷255 temperature thresold Solar sanitary hysteresis °C 0÷25.5 Solar collector overfill alarm °C 0÷255 threshold Minimum temperature threshold collector for activa-...
  • Page 35: Power Failure

    SHP M ECO Heat pump air/water inverters with axial fans If the pressure switch on the machine detects a pressure exceeding 42.8 bar the driver and the compressor are powered off and probe error E641 is displayed (Compressor discharge probe fault). The alarm is cleared when the pressure drops below 34 bar.
  • Page 36 SHP M ECO Heat pump air/water inverters with axial fans Code DESCRIPTION Block E651 Outdoor air probe failure Machine *E652 Mixer probe failure Machine E661 DHW probe failure Machine *E662 Solar storage tank probe failure Machine E671 Plant remote probe failure Machine *E672 Solar collector probe failure...
  • Page 37 SHP M ECO Heat pump air/water inverters with axial fans Register Format Range Name Description Note Firmaware versione Firmware release BYTE (H) Firmware sub-release Firmaware informa- tion BYTE (L) Firmware creation day BYTE (H) Firmaware creation month BYTE (L) Firmware creation year 80 ÷...
  • Page 38 SHP M ECO Heat pump air/water inverters with axial fans Register Format Range Name Description Note Active only if the setting of bit 3 is Sanitary call prohibition (without exiting 7201 (when the 7202 BIT MASK Santary disablig from the actual mode + SAN function) room temp.
  • Page 39 SHP M ECO Heat pump air/water inverters with axial fans Register Format Range Name Description Note High temperature E018 High discharge temperature of Cp2 E019 Inverted pressure transducers E020 Compressor 3 thermal protection E023 Fan 3 thermal protection E024 Pump 2 thermal protection E026 BIT MASK Alarms ⁴...
  • Page 40 SHP M ECO Heat pump air/water inverters with axial fans Register Format Range Name Description Note Module 2 probe 11 error E713 Link inverter 1 E801 Link inverter 2 E802 Link inverter 3 E803 Hardware fault inverter 1 E851 Hardware fault inverter 2 E852 Hardware fault inverter 3 E853...
  • Page 41 SHP M ECO Heat pump air/water inverters with axial fans...
  • Page 42 SHP M ECO Heat pump air/water inverters with axial fans...
  • Page 43 SHP M ECO Heat pump air/water inverters with axial fans...
  • Page 44 SHP M ECO Heat pump air/water inverters with axial fans...
  • Page 45 SHP M ECO Heat pump air/water inverters with axial fans...
  • Page 46 SHP M ECO Heat pump air/water inverters with axial fans...
  • Page 47 SHP M ECO Heat pump air/water inverters with axial fans...
  • Page 48 Fonderie Sime S.p.A - Via Garbo, 27 - 37045 Legnago (Vr) Tel. +39 0442 631111 - Fax +39 0442 631292 - www.sime.it...