Download Print this page

Omron D4N Datasheet page 7

Miniature safety limit switch
Hide thumbs Also See for D4N:

Advertisement

Characteristics
Degree of protection (See note 3.)
Durability
Mechanical
(See note 4.)
Electrical
Operating speed
Operating frequency
Contact resistance
Minimum applicable load (See note 6.)
Rated insulation voltage (U
)
i
Protection against electric shock
Pollution degree (operating environment)
Impulse withstand voltage (EN60947-5-1)
Insulation resistance
Contact gap
Vibration resistance
Malfunction
Shock resistance
Destruction
Malfunction
Conditional short-circuit current
Rated open thermal current (I
Ambient temperature
Ambient humidity
Weight
Note: 1. The above values are initial values.
2. Once a contact has been used to switch a standard load, it cannot be used for a load of a smaller capacity. Doing so may result in rough-
ening of the contact surface and contact reliability may be lost.
3. The degree of protection is tested using the method specified by the standard (EN60947-5-1). Confirm that sealing properties are suffi-
cient for the operating conditions and environment beforehand. Although the switch box is protected from dust or water penetration, do
not use the D4N in places where foreign material such as dust, dirt, oil, water, or chemicals may penetrate through the head. Otherwise,
premature wear, Switch damage or malfunctioning may occur.
4. The durability is for an ambient temperature of 5° C to 35° C and an ambient humidity of 40% to 70%. For more details, consult your
OMRON representative.
5. If the ambient temperature is greater than 35° C, do not pass the 3-A, 250-VAC load through more than 2 circuits.
6. This value will vary with the switching frequency, environment, and reliability level. Confirm that correct operation is possible with the ac-
tual load beforehand.
7. The mechanical durability of fork lever lock models is 10,000,000 operations min.
D4N
IP67 (EN60947-5-1)
15,000,000 operations min. (See note 7.)
500,000 operations min. for a resistive load of 3 A at 250 VAC (See note 5.)
300,000 operations min. for a resistive load of 10 A at 250 VAC
1 mm/s to 0.5 m/s (D4-1120)
30 operations/minute max.
25 mΩ max.
Resistive load of 1 mA at 5 VDC (N-level reference value)
300 V
Class II (double insulation)
Level 3 (EN60947-5-1)
Between terminals of the same polarity: 2.5 kV
Between terminals of different polarities: 4 kV
Between other terminals and uncharged metallic parts : 6 kV
100 MΩ min.
Snap-action: 2 x 0.5 mm min
Slow-action: 2 x 2 mm min
10 to 55 Hz, 0.75-mm single amplitude
2
1,000 m/s
2
300 m/s
min.
100 A (EN60947-5-1)
)
10 A (EN60947-5-1)
th
Operating: − 30° C to 70° C with no icing
Operating: 95% max.
Approx. 82 g (D4N-1120)
Approx. 99 g (D4N-5120)
min.
G-225