Download Print this page

Eterna PRSQMW3 Installation Instructions Manual

Power & colour temperature selectable emergency ip65 led utility fitting with multi-function sensor

Advertisement

Quick Links

EVENTUALLY, YOU MAY WANT TO
REPLACE THIS PRODUCT:
Regulations require the recycling of Waste from
Electrical and Electronic Equipment (European
"WEEE Directive" effective August 2005—UK
WEEE Regulations effective 2nd January 2007).
Environment Agency Registered Producer: WEE/
GA0248QZ.
WHEN YOUR PRODUCT COMES TO THE END OF
ITS LIFE OR YOU CHOOSE TO REPLACE IT, PLEASE
RECYCLE IT WHERE FACILITIES EXIST - DO NOT
DISPOSE WITH HOUSEHOLD WASTE.
LAMP REPLACEMENT:
The light source is designed to last the lifetime of the
luminaire.
The light source contained in this luminaire
shall only be replaced by the manufacturer,
service agent or a similar qualified person.
CAUTION, RISK OF ELECTRIC SHOCK.
INDUSTRIAL BATTERIES:
Within certain products Eterna Lighting Ltd places
lead acid, lithium ion, nickel cadmium & nickel
metal hydride batteries on the market. Industrial
batteries are subject to waste regulation under
the Waste Batteries and Accumulators Regulations
2009 and should be disposed of responsibly.
Purchasers may be able to dispose of their waste
industrial batteries locally via legitimate licensed
trade waste contractors. Eterna is obliged to take
back, free of charge and within a reasonable time,
waste industrial batteries of the same chemistry
supplied to a Purchaser, for treatment and recycling
and is required to do this in any calendar year new
industrial batteries are placed on the market. In
certain circumstances, this may include batteries
not originally supplied by Eterna. If any Purchaser
requires Eterna to take back Industrial batteries,
they should write to the Operations Director, Eterna
Lighting Ltd, Huxley Close, NN8 6AB, who will then
advise on the necessary arrangements for the
receipt, proper treatment and recycling of, the waste
industrial batteries.
See website for more information on
replacability and recycling
Email: sales@eterna-lighting.co.uk / technical@eterna-lighting.co.uk
www.eterna-lighting.co.uk
Visit our website:
Issue 0122
BATTERY REPLACEMENT:
If after routine operation check, the lamp does not
remain lit for the three hour period, a new battery
pack may be required.
01. Switch off the electricity at the mains (both
permanent live and switch live) and allow
batteries to fully discharge then reconnect to
supply and allow charging for 24 hours.
02. Test again for 3 hours, if light does not remain lit,
then change the battery pack as follows:
03. Remove the diffuser.
04. Remove the battery case from the gear tray,
remove the battery and cut the wires.
05. Write current date on the new battery pack and fit
a new battery with a suitable connector.
06 Refit gear tray and diffuser.
07. Restore power and allow charging for 24 hours.
08. Perform full operation check and update test
record.
REPLACEMENT BATTERY TYPE:
3.2V 1500mAh Lithium
CLEANING:
Clean this fitting only with a soft dry cloth.
Do not use any chemical or abrasive cleaners.
IF YOU EXPERIENCE PROBLEMS:
If you believe your product is defective, please return
it to the place where you bought it. Our Technical
Team will gladly advise on any Eterna Lighting
product, but may not be able to give specific
instructions regarding individual installations.
Made in China
INSTALLATION INSTRUCTIONS
A guide for qualified electricians
3 HOURS DURATION IN EMERGENCY MODE
Model:
PRSQMW3 / PRCIRMW3
OPSQMW3 / OPCIRMW3
Power & Colour Temperature Selectable Emergency
IP65 LED Utility Fitting with Multi-Function Sensor
These instructions are provided as a guideline to assist you.
PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLATION
AND RETAIN FOR FUTURE REFERENCE
Pack contents:
1 x Base
1 x Diffuser
1 x Maintenance check record

Advertisement

loading
Need help?

Need help?

Do you have a question about the PRSQMW3 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Eterna PRSQMW3

  • Page 1 Purchasers may be able to dispose of their waste industrial batteries locally via legitimate licensed IF YOU EXPERIENCE PROBLEMS: trade waste contractors. Eterna is obliged to take back, free of charge and within a reasonable time, If you believe your product is defective, please return waste industrial batteries of the same chemistry it to the place where you bought it.
  • Page 2: Installation

    07. Secure the fitting in place. Note if protection and persons with sensory, physical and/or mental it. Eterna Lighting cannot accept any liability for Brown LIVE against ingress of moisture is required, the heads...
  • Page 3: Understanding The Controls

    0Sec 10Sec 10Min OFF OFF CORRIDOR DIMMING LEVEL / STAND-BY DIMMING LEVEL Light can be dimmed to different levels after hold- time. Eterna Lighting Ltd RED DIRECTIVE - Microwave Occupancy Sensor Full declaration available at: www.eterna-lighting.co.uk/red-declaration...
  • Page 4 Product Product Code: Description: Product Location: Installation Installation Date: Test Duration: INSTALLATION, MAINTENANCE AND OPERATION CHECK RECORD Installed Year: Year: Year: Year: Year: Test Sign Date Sign Date Sign Date Sign Date Sign Date Short Short Short Short Short Short Short Short Short...
  • Page 5 CIRCULAR OPAL CIRCULAR PRISMATIC LED LAMP SPECIFICATIONS: LED LAMP SPECIFICATIONS: 1090 lm 1610 lm 1970 lm 1180 lm 1715 lm 2055 lm 3000K - 3000K - 3000K - 3000K - 3000K - 3000K - Luminaire lumens (with Luminaire lumens (with 1160 lm 1770 lm 2190 lm...
  • Page 6 SQUARE OPAL SQUARE PRISMATIC LED LAMP SPECIFICATIONS: LED LAMP SPECIFICATIONS: 1080 lm 1630 lm 1980 lm 1150 lm 1730 lm 2100 lm 3000K - 3000K - 3000K - 3000K - 3000K - 3000K - Luminaire lumens (with Luminaire lumens (with 1150 lm 1770 lm 2200 lm...

This manual is also suitable for:

Prcirmw3Opsqmw3Opcirmw3