CHAMP "QL Induction Lighting System"
Luminaires - VMVIG Series - 55 Watts
Installation & Maintenance Information
APPLICATION
Champ
VMVIG series luminaires are suitable for use in the following
®
hazardous (classified) areas as defined by the National Electrical Code
(NEC®), Canadian Electrical Code (CEC), and International
Electrotechnical Commission (IEC):
•
Class I Division 2 Groups A, B, C, D; Class I Zone 2 II
•
Class I Zone 2, AEx nR II, Ex xR II
•
IEC Zone 2, Ex nR II
To avoid the risk of fire, explosion, or electric shock, this
product should be installed, inspected, and maintained by a
qualified electrician only, in accordance with all applicable electrical
codes.
To avoid electric shock:
Be certain electrical power is OFF before and during installation and
maintenance.
Luminaire must be supplied by a wiring system with an
equipment grounding conductor.
To avoid burning hands:
Make sure globe or refractor and lamp are cool when performing
maintenance.
INSTALLATION
Mounting
1.
Mount the cover module in its support position.
•
Ceiling and Wall mount: Mark and drill desired location
on mounting surface. Secure with 5/16" bolts or lag
screws (not provided).
•
Pendant, Stanchion and Quad mount: Securely thread
onto the appropriate NPT size conduit. Tighten
setscrew located in the conduit hub. See figure 1.
SET
SCREW
IF 1462 • 10/03
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
WARNING
WARNING
OPEN
HINGE
GROUND
WIRES
FIGURE 1
Copyright © 2003, Cooper Industries, Inc.
Refer to the luminaire nameplate for specific classification
information, maximum ambient temperature suitability and
corresponding operating temperature (T-Code).
VMVIG series luminaire 4X / IP66 construction is designed for use
indoors and outdoors in Marine and Wet locations, where moisture, dirt,
corrosion, vibration and rough usage may be present.
VMVIG series luminaires are supplied for 120V 50-60Hz or 240V 50-60
Hz and are furnished complete with one Philips QL Induction Lighting
System in 55W.
To avoid explosion:
Make sure the supply voltage is the same as the luminaire
voltage.
Do not install where the marked operating temperatures exceed the
ignition temperature of the hazardous atmosphere.
Do not operate in ambient temperatures above those indicated on the
luminaire nameplate.
Install luminaire with lamp base up within 25º of vertical.
Use only the Philips QL Lighting System of the wattage specified on
the luminaire nameplate.
Use proper supply wiring as specified on the luminaire nameplate.
All gasket seals must be clean.
Before opening, electrical power to the luminaire must be turned off.
Keep tightly closed when in operation.
Wiring
1.
The VMVIG Champ-Pak luminaire is furnished complete with the
Philips QL Induction Lighting System, which consists of 3 parts:
a) Lamp (glass bulb)
b) Power Coupler
c) HF (high frequency) Generator
For proper operation the lamp must be properly seated on the
power coupler and for heat dissipation both the power coupler and
HP generator must be firmly mounted to luminaire. To make sure
nothing has loosened in shipment, check that the lamp is seated
properly and both the power coupler and HP generator mounting
screws are tight (20 in.-lbs.). Connect the green ground wire that is
attached inside the ballast housing to incoming ground. Connect
supply wires to the HF generator
as illustrated in the wiring diagram
on page 4 of these instructions.
For additional information specific
to the QL Lighting system itself,
refer to the Philips Lighting QL
System Instruction Sheet supplied
with the luminaire.
IF 1462
WARNING
FIGURE 2