Cooper Crouse-Hinds Hazard-Gard EVLPFB Installation & Maintenance Information

Low profile emergency lighting

Advertisement

Quick Links

EVLPFB Low Profile Hazard•Gard
Installation & Maintenance Information
APPLICATION
Low Profile HAZARD-GARD
listed for use in Class I, Division 1 & 2, Groups B (with GB suffix),
C, D, Class II, E, F & G, simultaneous presence, Class III, and
Wet locations as defined by the National Electrical Code
to the fixture nameplate for specific classifications information
and operating temperature (T) rating.
Low Profile HAZARD-GARD Fluorescent fixtures are supplied
with a choice of voltages (120 and 277) and wattages (52 or 64).
The 52 watt fluorescent fixture is also available in 220-240V,
50/60 Hz.
Low Profile HAZARD-GARD Fluorescent lighting fixtures are
suitable for operation in ambient temperatures (as measured at
mounting position) between 0°C (32°F) and 40°C (104°F), as
marked on the fixture nameplate.
The EVLPFB fixture is supplied with a battery back-up. When AC
power is interrupted, the fixture switches to a built-in battery
power supply to light one lamp, providing emergency lighting for
at least 90 minutes. When AC power is restored, the fixture
automatically switches from battery power to AC power. While
operating on AC power, the fixture circuitry recharges the battery.
IF 1414 • 5/00
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
®
emergency lighting fixtures are UL
Copyright © 2000, Cooper Industries, Inc.
Emergency Lighting
®
IMPORTANT SAFEGUARDS
READ AND FOLLOW ALL
SAFETY INSTRUCTIONS
®
. Refer
1.
Do not use this equipment for other than intended use.
2.
The use of accessory equipment not recommended by the
manufacturer may cause an unsafe condition.
3.
Electrical power must be turned OFF before and during
installation and maintenance.
4.
Equipment should be mounted in locations and at heights
where it will not readily be subject to tampering by
unauthorized personnel.
5.
Do not mount near gas or electric heaters.
6.
Install and seal all equipment in accordance with the
National Electrical Code articles pertaining to Hazardous
(Classified) Locations plus any other codes.
7.
Install only grounded wiring systems to supply the EVLPFB
light fixture.
8.
If possible, free installation area of hazardous atmospheres
before wiring to reduce the risk of accidental explosion due
to inadvertent shorting of battery during installation.
9.
Observe all battery handling precautions contained herein.
SAVE THESE INSTRUCTIONS
INSTALLATION
Note:
Low Profile HAZARD-GARD lighting fixtures should be installed,
inspected, and maintained by qualified and competent personnel.
To avoid electrical shock, be certain that power is OFF
before and during installation or before attempting any
maintenance
To avoid explosion, do not install where marked
operating temperatures exceed ignition temperatures
of hazardous atmospheres.
Operating the fixture in ambient temperatures above
those indicated on fixture nameplate will result in globe
temperature exceeding nameplate markings and will
shorten life of internal components.
To avoid excessive operating temperatures, fixture
must be installed with lamp base up within 25 degrees
of vertical position.
To avoid light failure, proper field wiring as specified on
fixture nameplate must be used.
IF 1414
!
WARNING
Page 1

Advertisement

loading
Need help?

Need help?

Do you have a question about the Hazard-Gard EVLPFB and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Cooper Crouse-Hinds Hazard-Gard EVLPFB

  • Page 1 EVLPFB Low Profile Hazard•Gard Emergency Lighting ® IF 1414 Installation & Maintenance Information SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE APPLICATION IMPORTANT SAFEGUARDS ® Low Profile HAZARD-GARD emergency lighting fixtures are UL READ AND FOLLOW ALL listed for use in Class I, Division 1 & 2, Groups B (with GB suffix), SAFETY INSTRUCTIONS C, D, Class II, E, F &...
  • Page 2 Install mounting module - pendant, ceiling, wall bracket, or stanchion in its support position and attach to conduit system. Secure with set screw, when provided. Pull wire in mounting position. Remove cover from ballast housing and remove connection block from cover by unscrewing the four captive screws. Pendant Mounting Module...
  • Page 3 REFLECTOR INSTALLATION O-Ring Seal Optional Reflectors: • 30° Angle RA739 • Dome RD739 Optional reflectors are attached to the Low Profile HAZARD- GARD fixtures as follows: Place reflector in position on fixture lower housing. When correctly placed, all three tabs of reflector are located between reflector mounting plates.
  • Page 4 BATTERY PACK MAINTENANCE RELAMPING: EVLPFB SERIES Disconnect power to fixture and allow unit to cool completely. Loosen screw that secures locking tab. Lower tab and WARNING retighten screw to hold locking tab temporarily out of the Fixture is supplied with battery back-up (EVLPFB) system, way.