Type ME64 Type ME64 ontent THE OPERATING INSTRUCTIONS ......................5 Symbols ............................5 1.2 Definition of terms ........................5 INTENDED USE ............................6 BASIC SAFETY INSTRUCTIONS ......................7 GENERAL NOTES...........................8 4.1 Contact address ...........................8 4.2 Warranty ............................8 4.3 Information on the Internet ......................8 PRODUCT DESCRIPTION ........................9 5.1 Switch for changing over the voltage supply ................9 TECHNICAL DATA ..........................10 6.1 Standards and directives ......................10 6.2...
Page 4
Type ME64 9.1 Bürkert Communicator user interface ..................22 9.2 Connecting the device to the “Bürkert Communicator” ............23 9.3 User levels in the Communicator ....................23 9.3.1 Change user level .......................23 9.3.2 Changing user password ....................23 9.3.3 Set active user level ....................24 9.4 Base settings of the input module ....................24 9.4.1 Sampling time configuration ..................24 9.4.2 Configuration of nominal operating mode ..............24 9.4.3 Configuration of input filter ..................25 9.4.4 Configuration of flow input ..................25 9.4.5 Configuration of channel name ...................25...
Type ME64 The operating instructions THE OPERATING INSTRUCTIONS The operating instructions describe the entire life cycle of the device. Keep these instructions ready to hand at the operation site. Important safety information! ▶ Carefully read these instructions. ▶ Above all, observe the safety instructions, intended use and operating conditions. ▶...
Type ME64 Intended use INTENDED USE The I/O module Type ME64 FieldConnect collects, converts and compares physical measurement data from external sensors and transfers this data to external actuators or büS participants via the büS interface. ▶ Use the device only as intended. Non-intended use of the device may be dangerous to people, nearby equipment and the environment. ▶ Use the device only in conjunction with third-party devices and components recommended or approved by Bürkert.
Type ME64 Basic safety instructions BASIC SAFETY INSTRUCTIONS These safety instructions do not take into account any unforeseen circumstances or events that occur during installation, operation and maintenance. The operator is responsible for observing the location-spe- cific safety regulations, also with reference to personnel. General hazardous situations. To prevent injuries, observe the following: ▶ Use the device only when it is in perfect condition and in accordance with the operating instructions. ▶...
Type ME64 General notes GENERAL NOTES Contact address Germany Bürkert Fluid Control Systems Sales Center Christian-Bürkert-Str. 13-17 D-74653 Ingelfingen Phone + 49 (0) 7940 - 10-91 111 Fax + 49 (0) 7940 - 10-91 448 E-mail: info@burkert.com International You can find the international contact addresses on the Internet at: country.burkert.com Warranty A precondition for the warranty is that the device is used as intended in consideration of the specified oper- ating conditions. Information on the Internet Operating instructions and data sheets for the Bürkert products can be found on the Internet at: country.burkert.com English...
Type ME64 Product description PRODUCT DESCRIPTION The I/O module Type ME64 FieldConnect collects digital values of physical measurement data from external sensors and transfers this data to external actuators or büS participants via the büS interface. The module is designed for decentralised use in the process environment. It is easy to install and increases process reliability due to integrated monitoring and diagnostic functions.
Type ME64 Technical Data TECHNICAL DATA Standards and directives The device complies with the valid EU harmonisation legislation. In addition, the device also complies with the requirements of the laws of the United Kingdom. The harmonised standards that have been applied for the conformity assessment procedure are listed in the current version of the EU Declaration of Conformity/ UK Declaration of Conformity.
Type ME64 Technical Data Digital inputs Number of inputs Connection Socket M12, 5-pole, A-coded max. current consumption < 7 mA Voltage input 0…30 V Suitable for 2-wire proximity switches Yes Suitable for 3-wire proximity switches yes Short circuit-proof proximity switch feed Number of frequency inputs Frequency Max. 2.5 kHz Switching threshold = 10…30 V,...
Type ME64 Installation INSTALLATION WARNING Risk of injury due to improper installation. Only trained technicians may perform installation work. ► Perform installation work using suitable tools only. ► Installing the device The device will be delivered fully installed. Modifications to the device are only permitted to be carried out by Bürkert. → Install the device on a level surface using 2 screws (M4) and 2 flat washers (according to DIN 125). Observe the maximum tightening torque of 1Nm. → Earth the device via the earthing lead. The earthing lead is located at the lower device attachment. CAUTION Malfunction due to electrostatic discharge.
Type ME64 Installation Electrically connecting the device Requirements for UL-certified devices: ▶ Only connect devices with a UL-certified cable (CYJV or PVVA) with suitable nominal values. ▶ Maximum permitted cable temperature is 105° C. ▶ Do not lay Ethernet cables used for communication outside buildings. ▶ Galvanically isolate external circuits connected to ports from mains circuits, in order to protect them against isolation breakdown in the communication network. ATTENTION Prerequisite for the fault-free functioning of the device and to avoid interference issues: ▶...
Type ME64 Installation Connections X1-X8 (IN) Function: digital inputs A/B, operating voltage 24 V View Assignment Function 24 V Supply IN B Digital input channel B Supply IN A Digital input channel A Shielding Table 3: Connections X1 to X8 7.3.2 Connecting the external sensors → See assignment of the connections X01 (IN), X02 (OUT) in Chapter „7.3“ auf Seite 14. Connecting 2-wire and 3-wire sensors 3 Wire 2 Wire...
Type ME64 Installation Combining ME6x modules 7.4.1 Module connections for the power supply ME63 ME64 ME66 Fig. 3: Power supply via büS connection ME63 ME64 & ME66 M12-A, socket, büS/CANopen and 24 V X1-X3; M12-A, plug, büS/CANopen IN, max. 4 A, for DC, max. 4 A, for connection of a device connection of büS/ CANopen network X5-X8 via büS/CANopen M12-A, plug, büS/CANopen and 24 V DC, M12-A, socket, büS/CANopen OUT, max.
Page 17
Type ME64 Installation ME63 ME64 & ME66 Fig. 4: Power supply via X03 Connection Description X03 (IN) M12-L, plug, power IN, max. 32 A, for power supply input X04 (OUT) M12-L, socket, power OUT, max. 32 A, for power supply for other devices ATTENTION Damage to device ▶ The L-coded M12 connection (X03, X04) is designed for connecting 2 power supplies, each up to max. 16 A. Do not exceed these values. English...
Type ME64 Installation 7.4.2 Simplified power supply plan When modules in the ME6x product series are combined, the information provided in this chapter must be followed. For type ME63, the supply can be either via X03 (max. 2x16A) or X4 (max. 4A). • Attention: A supply via both is prohibited. For Type ME64, Power 1 and Power 2 are two separate circuits with common ground. • Both supplies are routed separately to the module. Power 1 supplies ports X1-X8 (and the internal electronics assembly of the module). •...
Page 19
Type ME64 Installation Reverse protection - ME63 If both supplies (A-coded and L-coded) are connected, it is not permitted for any return flow to occur via the A-coded supply. With the ME63 type, this is prevented via reverse protection. If the modules are only supplied via the M12 A-coded (X4) supply, the reserve protection function switches over automatically. Power supply via X01 (AUX power) - ME64 & ME66 The power supply is activated via port X03 for the modules in delivery condition. ATTENTION Input cannot be made via both ports at the same time. If the modules are supplied via port X01, the switch must be changed over. Underneath the light blue side panel, there is a switch for changing over the module supply from X03 to port X01 (AUX power). „7.4.2 Simplified power supply plan“ ATTENTION Damage to the switch for AUX power. A current >4A will damage the switch. ▶...
Type ME64 Installation 7.4.3 Combining ME66 modules In this instance, the switch must be changed in order to use AUX power. „7.4.2 Sim- plified power supply plan“ only data = 2x16 A = 2x16 A Fig. 6: Example for the combination of ME66 modules English...
Type ME64 Installation Combining different ME modules In this instance, the switch must be changed in order to use AUX power. ME66 ME64 max. ME63 only data ME66 ME64 ME66 only data only data = 2x16 A = 2x16 A = 2x16 A = 32 A Fig.
Type ME64 Start-up with an external controller START-UP WITH AN EXTERNAL CONTROLLER The I/O module Type ME64 FieldConnect can be used in büS networks or CANopen networks. Information on CANopen can be found at: → ME64 → Downloads “Operating instructions” → country.burkert.com CANopen network configuration In conjunction with the following Bürkert devices, the I/O module can be integrated into existing control systems: • Fieldbus gateway Type ME43 • Fieldbus gateway Type ME63 FieldConnect • Valve island Type 8652 AirLINE with büS and fieldbus connection...
Type ME64 Start-up with Bürkert Communicator START-UP WITH BÜRKERT COMMUNICATOR The Bürkert Communicator software can be downloaded free of charge from the Bürkert website. In addition to the software, the USB-büS interface kit, available as an accessory, is required. The USB-büS interface kit can be ordered from Bürkert as an accessory (see Page 38). This chapter only describes basic use of the Bürkert Communicator. Detailed information on using → the Bürkert Communicator software can be found on the Bürkert website at: country.burkert.com 8920 → Downloads “Operating instructions” Bürkert Communicator user interface Add interface (connect with büs stick) Menus Navigation area Detailed views Parameter Diagnostics Maintenance Configuration areas of the device Device Fig. 9: Example of a user interface of the Bürkert Communicator software...
Type ME64 Start-up with Bürkert Communicator Connecting the device to the “Bürkert Communicator” The Bürkert Communicator can be connected to the device via a büS network or with the büS stick. → Install the Bürkert Communicator on the PC. → Use the USB-büS-interface to establish the connection between the device and the PC. Not required for the devices in a büS network. → Start the Bürkert Communicator. → In the menu bar, click the icon for Add interface. → Select or büS via the network. büS stick →...
Type ME64 Start-up with Bürkert Communicator 9.3.3 Set active user level Required user level: “Installer” Options > Password manager ... → If necessary, enter the installer password. Change user password window appears. → Disable the password at the desired user level. User password Active user level during program start No user password disabled User “Advanced user” disabled Advanced user “Installer”...
Type ME64 Start-up with Bürkert Communicator 9.4.3 Configuration of input filter For nominal operating mode “Frequency”, “Flow” or “Flow totaliser”. To reduce signal fluctuations, one input filter with PT1 behaviour can be enabled per channel. The filter response time can be set from 1 to 10,000 ms, but must be greater than the set sample time. Inputting 0 ms deactivates the filter. 9.4.4 Configuration of flow input For nominal operating mode “Flow” or “Flow totaliser”. → Enter K factor in [Pulses / Litre]. A 2-point calibration is subsequently possible under: Digital inputs >...
It does not describe the basic operation of the software. Detailed information on using the Bürkert Communicator software can be found on the Bürkert → website at: country.burkert.com 8920 → Downloads “Operating instructions” The overview below shows the menus that are displayed in the “installer” user level. This user level has the highest authorisation level.
Page 28
Type ME64 Bürkert Communicator menus Menu Description Menu only available for nominal operating modes “Frequency”, “Flow” and Filter response time “Flow totaliser”. The filter response time can be set from 1 to 10,000 ms, but must be greater than the set sample time. Inputting 0 ms deactivates the filter. Menu only available for nominal operating modes “Flow” and “Flow K factor totaliser”. The K factor is a value [pulses/litre] by which the signal value of the sensor is multiplied to convert it to the real process value [l/min]. If a value ≠ 0 is entered, the values of the 2-point calibration (following 4 menu options) are ignored. Lower flow rate Menus only available for nominal operating modes “Flow”...
Page 29
Type ME64 Bürkert Communicator menus Detailed view “Maintenance” This detailed view is not available for nominal operating mode “Digital”. Menu Description Flow input calibration 2-point-calibration of flow inputs. Calibration data will not be applied if the K factor is valid ( not 0 ). A wizard guides users through the menu. It is only possible to reset the pulse counters when the nominal operating Reset pulse counters mode “Pulse counter” has been configured.
Type ME64 Bürkert Communicator menus 10.2 Menus in the “General settings” configuration area Detailed view “Parameter” Menu Description Status LED Operation mode Setting the various operating modes: NAMUR, fixed colour and LED off. Parameterisation of the device as a büS participant. büS Displayed name Device name under which the device is displayed in Bürkert Communicator. Location Device location. Shown in Bürkert Communicator beneath the device name. Description The input window can be used to describe the device or for additional information on the device.
Page 31
Type ME64 Bürkert Communicator menus Menu Description Configuration of the cyclic process data objects: PDO configuration PDO 1 The information from channels 1 to 16 is transmitted as bit fields in the PDO 1 object. PDO 2 This includes multifunction inputs 2, 4, 6, 8, 10, 12, 14 and 16, when they PDO 3 are configured as digital inputs. When the multifunction inputs are assigned another input function (e.g. Frequency), the information from these channels are transmitted in other PDO objects: PDO 2 for channels 1 and 2, and PDO 3 for channels 9 and 10. The corresponding bit values in the PDO 1 object are invalid in this case and are to be ignored. PDO 2 and PDO 3 are then only generated by the device if the multi- function inputs are not configured as digital inputs.
Page 32
Type ME64 Bürkert Communicator menus Detailed view “Diagnostics” Menu Description Device status Information on the device status. Operating duration Indicates the operating duration over the entire life cycle of the device. Operating duration since Indicates the operating duration since the last boot. last boot Device temperature Current device temperature (not the ambient temperature!). Voltage drops Indicates the number of voltage drops since the last reboot.
Page 33
Type ME64 Bürkert Communicator menus Detailed view “Maintenance” Menu Description Device information Indicates device-specific data. Displayed name Indicates the name entered for the device. The name is entered under > > > Displayed name. General settings Parameter büS Identification number Indicates the identification number of the device. Indicates the serial number of the device. Serial number Firmware identification Display of firmware identification number.
Type ME64 Display elements DISPLAY ELEMENTS Type ME64 has the following LEDs for diagnostics on the device status: • LED for indicating the channel status (1 LED per channel). • LED for indicating the device status. Channel status LED channel A LED device status Channel status LED channel B Fig. 10: Display elements Type ME64 11.1 LEDs for indicating the channel status...
Type ME64 Display elements Indication in line with Device status Meaning NE 107 Colour Colour code blue Device config- Updated device configuration cannot be saved. uration cannot Not possible to transfer the configuration when swapping be managed devices. green Diagnostics Device is in error-free operation. active Status changes are highlighted in colour. Messages are transmitted via büS/CANopen. white Diagnostics Device is switched on.
Type ME64 Troubleshooting TROUBLESHOOTING Problem Possible cause Measure Namur LED remains off Switch for changing over the oper- Set correct voltage input. despite operating voltage ating voltage (underneath light blue being applied. panel) set incorrectly. Incorrect voltage input connection Use the correct connection. used. NAMUR LED goes out The power supply drops out peri- Use power supply with adequate...
Type ME64 Device replacement DEVICE REPLACEMENT For further information on replacing devices, see the operating instructions ”Central configuration management of Bürkert devices” (Type ME64) country.burkert.com Clients can be replaced in a büS network without configuration work. The provider reads and saves the configurations of a connected client. If the client is replaced, the provider detects the replacement and transfers the saved configuration to the new device. Type ME64 is the client, fieldbus gateway ME63 the provider. Prerequisites The following prerequisites must be met for the configuration to be transferred to a replacement device: • The replacement device has the same identification number and a different serial number from the prede- cessor device. • The function “configuration provider” is enabled in the provider (via Bürkert Communicator). • The provider has an SD card. Device replacement process •...
Type ME64 Accessories ACCESSORIES ATTENTION Property damage due to incorrect parts. Incorrect accessories and unsuitable spare parts may cause damage to the device. ▶ Use only original accessories and original spare parts from Bürkert. büS accessories Article Quantity Order no. USB-büS interface kit 1 772426 (including power supply unit, büS stick, termination resistor, Y-distributor, 0.7 m cable with M12 plug) USB-büS interface kit 2 772551 (including büS stick, termination resistor, Y-distributor, 0.7 m cable with M12 plug) büS cable, angled M12 (stranded wire to female connector) 0.7 m 772626 büS cable (stranded wire to M12 female connector)
▶ Store the device in a dry and dust-free location. Storage temperature: –30…+80 °C Environmentally friendly disposal ▶ Follow national regulations regarding disposal and the environment. ▶ Collect electrical and electronic devices separately and dispose of them as special waste. Further information at country.burkert.com. English...