4.21.2 Dancer control (Pr. 44, Pr. 45, Pr. 128 to Pr. 134)

Performs PID control by feedbacking the position detection of the dancer roller, controlling the dancer roller is in the
specified position.
Parameter
Name
Number
Second
44
acceleration/
deceleration time
Second
45
deceleration time
PID action
128
selection
PID proportional
129 ∗1
band
130 ∗1
PID integral time
131
PID upper limit
132
PID lower limit
Special operation and frequency control
Initial Value
FR-E740-095 or less
5s
FR-E720S-110 or less
0 to 3600/360s
FR-E740-120 and 170 10s
FR-E740-230 and 300 15s
0 to 3600/360s This parameter is the deceleration time of the main
9999
0
0.1 to 1000%
100%
0.1 to 3600s
1s
9999
9999
Setting
Range
This parameter is the acceleration time of the main
speed during dancer control. It will not function as
second acceleration/deceleration time.
speed during dancer control. It will not function as
9999
second deceleration time.
0
PID action is not performed
PID reverse
20
action
Measured value (terminal 4)
PID forward
Set value (terminal 2 or Pr. 133)
21
action
PID reverse
Addition
40
action
method: fixed
PID forward
Addition
41
action
method: fixed
PID reverse
Addition
42
action
method: ratio
PID forward
Addition
43
action
method: ratio
PID reverse
50
Deviation value signal input
action
(L
ON
PID forward
51
communication)
action
PID reverse
60
Set point and measured value input
action
(L
ON
PID forward
61
communication)
action
If the proportional band is narrow (parameter
setting is small), the manipulated variable varies
greatly with a slight change of the measured value.
Hence, as the proportional band narrows, the
response sensitivity (gain) improves but the
stability deteriorates, e.g. hunting occurs. Gain Kp
= 1/proportional band
9999
No proportional control
When deviation step is input, time (Ti) is the time
required for integral (I) action to provide the same
manipulated variable as the proportional (P) action.
As the integral time decreases, the set point is
reached earlier but hunting occurs more easily.
9999
No integral control.
Maximum value
If the feedback value exceeds the setting, the FUP
0 to 100%
signal is output. The maximum input (20mA/5V/
10V) of the measured value (terminal 4) is
equivalent to 100%.
9999
No function
Minimum value
If the process value falls below the setting range,
0 to 100%
the FDN signal is output. The maximum input
(20mA/5V/10V) of the measured value (terminal 4)
is equivalent to 100%.
9999
No function
Description
For dancer control
set point (Pr. 133),
measured value
(terminal 4)
main speed (speed
command of the
operation mode)
W
, CC-Link
ORKS
W
, CC-Link
ORKS