Lifting; Generator Set Inspection; Location And Mounting; Mounting Area - Kohler 6VSG Installation Manual

Dc generator sets
Hide thumbs Also See for 6VSG:
Table of Contents

Advertisement

1.2 Lifting

WARNING
Model
6VSG
Figure 2
Approximate Weights
Approximate generator set weights are shown in Figure 2. Use lifting bars inserted through the holes in the skid to lift the unit.
See the dimension drawings in the Installation Drawings section for lifting hole locations.

1.3 Generator Set Inspection

Complete a thorough inspection of the generator set. Check for the following:
1.
Inspect the generator set for loose or damaged parts or wires. Repair or tighten any loose parts before installation.
2.
Check the engine oil. Fill, if necessary, with the recommended viscosity and grade of oil. Use synthetic oil, API
(American Petroleum Institute) Service Class SG or higher. See TP-6843, Operation Manual, for additional information.

1.4 Location and Mounting

Install the generator set outdoors. Choose a location that is away from any building or structure and near the incoming gas
service. Allow clearance beyond the exhaust end of the generator set. Locate the generator set so that the hot exhaust does not
blow on plants or other combustible materials. Do not install the generator set where exhaust gas could accumulate and seep
inside or be drawn into a potentially occupied building.
Refer to your local codes and ordinances. See the figure titled: Dimension Drawing ADV-8060, Sheet 3 for the minimum
clearance from structures and non-combustible materials.
DO NOT locate the generator set near patios, decks, play areas, or animal shelters. Keep items such as lawn furniture, toys, sports
equipment, and all combustible materials away from the generator set exhaust outlet.
Remind family members, children, and visitors to use caution near the generator set. Generator sets will start automatically during exercise
periods and power outages. Some generator set components become hot when the generator set is running and remain hot for a time after
the generator set shuts down.
1.4.1

Mounting Area

Install the generator set on a single, level concrete mounting pad. This method provides maximum stability and ensures correct
cooling air flow through the generator set. The recommended mounting pad dimensions are shown in the dimension drawings
in the Installation Drawings section.
1.4.2

Vibration Isolation

The generator set is equipped with neoprene vibration isolators. Connections between the generator set or its mounting base
and any conduits or fuel lines must include flexible sections to prevent breakage and to isolate vibration.
14
Unbalanced weight.
Improper lifting can cause severe injury or death and equipment damage.
Do not use lifting eyes. Lift the generator set using lifting bars inserted through the lifting
holes on the skid.
Weight, kg (lb.)
190 (420)
Notice
TP-6842
9/21