Installation And Start-Up Outline; Physical Mounting - Distech Controls Security EC-BOS-602AX Hardware Installation Manual

Remote io module
Table of Contents

Advertisement

Module Connection Precautions
Module Connection Precautions
Avoid "hot" plug-in or removal of any expansion module from the EC-BOS
Caution
(or other expansion module), whenever a system is operational.
Do not connect more than 15 expansion modules (Remote IO Security Modules
included) to an EC-BOS
supported in software.

Installation and Start-up Outline

If installing the EC-BOS
Note
the EC-BOS-602/616
controller.
The major steps to installing and starting the Remote IO Security Module, are outlined as follows:
1.
Physically mount the Remote IO Security Module module onto DIN rail. See
4. If directly attaching to other modules, ensure that the 6-position end connector(s) are properly seated
into the end connectors of the other units. Note the previous
Make wiring connections for grounding, security I/O wiring, and power. See
2.
Apply power and perform an initial checkout. See
3.

Physical Mounting

Mount the Remote IO Security Module in a Distech Controls Security Enclosure (model Large or Medium). See
the enclosure installation documents listed in
All U.S. Installations: For a UL Listed system (UL 294)
Note
Module (Remote IO Security) in a
Security controller and any other expansion modules. If installed in any other enclosure (even one with
the same listing), UL listings are voided! Also refer to the
If needed, you can plug the Remote IO Security Module into another assembly of modules already mounted.
See
Figure 1
on page 5. It it not necessary to remove the cover before mounting.
Procedure 1
provides step-by-step mounting instructions for the Remote IO Security Module on an installed DIN
rail.
Procedure 1
To mount on DIN rail
Position the Remote IO Security module on the rail, tilting to hook DIN rail tabs over one edge of the
Step 1
DIN rail
(Figure
Use a screwdriver to pry down the plastic locking clip, and push down and in on the Remote IO
Step 2
Security, to force the locking clip to snap over the other edge of the DIN rail.
Slide the Remote IO Security module along the DIN rail to its intended location, as one of the following:
Step 3
If left-most module on a rail of a model Medium or Large enclosure, slide it to the far left, such that its
mounting-tab holes align with tapped holes in the enclosure.
4
AX
Security controller. This is the maximum number of modules
AX
Security and Remote IO Security Module at the same time, please refer to
AX
Hardware Installation Guide document to install the EC-BOS
"Related Documentation,"
Distech Controls Security Enclosure
1).
Updated: January 2014
"Module Connection Precautions"
"Power Up and Initial Checkout"
page 2.
you must mount
"UL Requirements"
Remote IO Security Module Hardware Installation Guide
Installation and Start-up Outline
AX
Security
AX
Security
"Physical Mounting"
on page
on page 4.
"Wiring Overview,"
page 7.
on page 18.
the Remote IO Security
, as well as the EC-BOS
section on page 19.
Part Number 05DI-HISCRIO-22
AX

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Security EC-BOS-602AX and is the answer not in the manual?

This manual is also suitable for:

Security ec-bos-616ax

Table of Contents