Cycle Component Function Explanation - Samsung AM100BXMWGH/EU Service Manual

Table of Contents

Advertisement

Cycle Diagram

7-3 Cycle Component Function Explanation

1. Accumulator : Separating the incoming liquid refrigerant to the compressor in order to prevent liquid refrigerant.
2. Oil Separator : Separating the oil from the refrigerant discharged from the compressor, and the separated oil is returned
to the compressor.
3. Intercooler : Supercooled liquid refrigerant through the heat exchanger and makes the medium pressure gas refrigerant
injected into the compressor.
4. IPM Cooler : IPM (Intelligent Power Module) by cooling to prevent overheating.
5. High/Low Pressure Sensor : Measure high/low Pressure of system.
6. High Pressure Switch : Suspend immediately for protection of system if high pressure of system exceeds setting value.
7. Outdoor EEV (Main EEV) : Adjust the incoming refrigerant to the outdoor heat exchanger during heating operation.
8. EVI EEV : By adjusting the amount of refrigerant passing through the Subcooler to obtain the degree of supercooling and
adjust the amount of gas refrigerant entering to the compressor.
9. 4Way Valve : Change the direction of flow of the refrigerant to the cooling / heating operation.
10. ARV (Accumulator Oil Return Valve) : Remaining at the bottom of the Accumulator recovered oil to the compressor.
11. MainCooling Valve : In the main cooling operation, sending the high pressure refrigerant to indoor unit in heating mode.
12. Outdoor EEV Valve : In the main cooling operation, It's closed so that the Outdoor EEV Valve can control the amount
13. Hotgas Valve : Sending the high pressure gas to low pressure pipe in order to protect low pressure.
14. Hotgas Valve 2 : In the cooling operation, changing high pressure pipe to low pressure pipe.
15. EVI SOL V : This valve opens when using the vapor Injection.
16. EVI BYPASS V : This valve opens in the sub cooling control. It's closed when using the vapor injection.
17. Discharge Temperature Sensor : Measure the temperature of the refrigerant discharged from the compressor.
18. Suction Temperature Sensor : Measure the temperature of the refrigerant to the compressor suction.
19. Cond. Out Temperature Sensor : Measure the temperature of the outdoor heat exchanger of the air conditioning opera-
20. EVI In/Out Temperature Sensor : Measure the temperature of the refrigerant inlet and outlet of the Subcooler.
21. Liquid Pipe Temperature Sensor : Measure the temperature of supercooling refrigerant in the outdoor unit of the air
22. Comp. Top Temperature Sensor : Measure the temperature of compressor top cover.
23. Ambient Temperature Sensor : Measure the outdoor temperature.
24. Water Temperature Sensor : Plate Heat Exchanger internal temperature measurement
25. Control box temp. Sensor : Control box internal temperature measurement, thermal protection used for the control.
26. Receiver : Storing the refrigerant piping system, a stable liquid refrigerant supply
27. Liquid Tube Valve : Refrigerant in the outdoor unit side, the indoor unit during heating operation to rotate the valve
operation.
7-2
of the refrigerant.
tion.
conditioning.