Specific installer safety instructions

3.1.1 Installation space requirements

Installer and user reference guide
16
CAUTION
Field-made refrigerant joints indoors shall be tightness tested. The test method shall
have a sensitivity of 5 grams per year of refrigerant or better under a pressure of at
least 0,25 times the maximum allowable pressure. No leak shall be detected.
CAUTION
The total refrigerant charge and/or releasable charge m
exceed the requirements for minimum floor area of the smallest room that is served.
For minimum floor area requirements for indoor units, see the installation and
operation manual of the outdoor unit.
NOTICE
The pipework shall be securely mounted and guarded protected from physical
damage.
Keep the pipework installation to a minimum.
in the system cannot