Factory Settings - ebm-papst K3G560-RA25-21 Operating Instructions Manual

Table of Contents

Advertisement

K3G560-RA25-21
Fig. 2: Connecting wires to terminals
; Seal the terminal box.
4.3.3 Cable routing
Water must be prevented from reaching the cable gland along the cable.
NOTE
Damage caused by moisture penetration.
Moisture can penetrate into the terminal box if water is
constantly present at the cable glands.
→ To prevent the constant accumulation of water at the cable
glands, the cable should be routed in a U-shaped loop
wherever possible.
→ If this is not possible, a drip edge can be produced by
fitting a cable tie directly in front of the cable gland for example.

4.4 Factory settings

Factory settings made for the device by ebm-papst.
Mode parameter set 1
PWM control
Mode parameter set 2
PWM control
Fan/device address
1
Max. PWM / %
100
Min. PWM / %
0
Save set value to
Yes
EEPROM
Set value requirement
Analog (linear)
Direction of action
Positive (heating)
parameter set 1
Direction of action
Positive (heating)
parameter set 2
Item no. 52443-5-9970 · ENU · Change 209539 · Approved 2021-02-10 · Page 8 / 14
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
Operating instructions

Advertisement

Table of Contents
loading

Table of Contents