Factory Settings - ebm-papst K3G630-PC08-03 Operating Instructions Manual

Table of Contents

Advertisement

K3G630-PC08-03
Wire-end ferrules
0.25 mm²
without insulating
collar,
in accordance with
DIN 46228-1 for
flexible cable
NOTE
Crimping and pressing forms of the wire-end ferrules
For flexible control and relay cables, from a cable cross-section
of 1.0 mm², a trapezoid crimp is required to ensure correct
installation on the connector.
Fig. 3: Trapezoid crimp
4.3.3 Connect cables to terminals
WARNING
Live terminals and connections even with device
switched off
Electric shock
→ Wait five minutes after disconnecting the voltage at all poles
before opening the device.
; Open the terminal box.
; Remove the cap from the cable gland.
; Only remove caps where cables are fed in.
Fig. 4: Installing the connectors in the terminal box. The connectors
must engage properly.
; Depending on the cable diameter, the seals included in the terminal
box must be inserted into the cable gland if necessary.
; Route the cable(s) (not included in the scope of delivery) into the
terminal box.
; Ensure separate routing of the supply cable(s) and the cables for
status contact and control interface. Depending on the requirements for
the end device, the physical separation of these cables in the terminal
box may be mandatory. Use the partitions inside the terminal box as
an aid to routing for this purpose.
; First connect the protective earth "PE". Tightening torque 3.5 ±0.4 Nm
Item no. 56607-5-9970 · ENU · Change 209539 · Approved 2021-02-10 · Page 9 / 16
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
Operating instructions
1.5 mm²
; Connect the cables to the corresponding terminals. Use a
Fig. 5: Connection of cables at terminals
; There must not be any tensile stress between the terminal and the
; The cable glands must be tight.
; Fit the terminal box cover, making sure that the sealing surfaces are
; Screw in the four screws (for tightening torque, see Chapter 3.1
4.3.4 Cable routing
Water must be prevented from reaching the cable gland along the cable.

4.4 Factory settings

Factory settings made for the device by ebm-papst.
Mode parameter set 1
Mode parameter set 2
Fan/device address
Max. PWM / %
Min. PWM / %
Save set value to
EEPROM
Set value requirement
Direction of action
parameter set 1
Direction of action
parameter set 2
screwdriver to do so. When connecting, make sure the wires do not
splay out. Insert the strands until they meet with resistance.
cable gland. The cable must be provided with strain relief.
clean.
Product drawing).
NOTE
Damage caused by moisture penetration.
Moisture can penetrate into the terminal box if water is
constantly present at the cable glands.
→ To prevent the constant accumulation of water at the cable
glands, the cable should be routed in a U-shaped loop
wherever possible.
→ If this is not possible, a drip edge can be produced by
fitting a cable tie directly in front of the cable gland for example.
PWM control
PWM control
01
100
5
Yes
Analog (linear)
Positive (heating)
Positive (heating)