Programmable Z Divider; Pegel Conversion Z Puls (Z Divider: All Off); Setting The Z Divider - Hohner HM210IT Manual

Level converter, direction signal decoder and programmable pulse divider
Table of Contents

Advertisement

6.

Programmable Z Divider

6.1.

Pegel conversion Z Puls (Z Divider: all OFF)

If the Z pulse have to be switched unchanged from the input to the output (no division, no
change in length and position), then the DIL switch position listed below must be chosen
DIL4 (right 8-pole)
1
2
3
4
OFF
OFF
OFF
OFF
The output at the level conversion can be set to zero (ZOUT = Low) with the control input
X2(3) ZERO_Z = High.
The function is active as long as there is a high level at the control input. The Z pulse can be
trimmed by switching.
6.2.

Setting the Z Divider

The programming of the Z divider is subject to the same rules as the programming of the
A/B divider.
DIL4 (right 8-pole)
1
2
3
4
ON
OFF
OFF
OFF
OFF
ON
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
OFF
ON
ON
OFF
ON
ON
ON
ON
ON
ON
ON
Rev. 1
Divider [Z]
5
6
7
8
OFF
OFF
OFF
OFF
Divider [Z]
5
6
7
8
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
HM210IT User's Manual
Comment
Binary value
ZIN = ZOUT (ZERO_Z = Low)
Comment
Binary value
Divider => 1: Binary value +1
1 : 2
1 : 3
1 : 4
1 : 253
1 : 254
1 : 255
1 : 256
www.hohner.it
.