13.4 seer2 single-packaged air conditioner and gas furnace system with r-454b refrigerant single phase 2-5 nominal tons (sizes 24-60) three phase 3-5 nominal tons (sizes 36-60)

Advertisement

PY5G--B: Installation Instructions
Superheat charging table is derived from optimum performance point. (95°F [35°C] outdoor ambient and (80°F [27°C] dry bulb; 67°F [19°C] wet bulb indoor condition.)
Where a dash (-) appears do not attempt to check charge or charge unit under these conditions using the superheat method. (Weigh in method should be used.)
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Table 10 – Cooling Charging Chart
29
A240114
A240115