Ach550/Acs320 Vfd Diagnostics; Correcting Faults; History - Carrier 48TC 07 Installation, Start-Up And Service Instructions Manual

Variable frequency drive (vfd) factory-installed option 2-speed motor control for 2-stage cooling rooftop units
Hide thumbs Also See for 48TC 07:
Table of Contents

Advertisement

5.
The text "Downloading Parameters (partial)" will be dis-
played with a progress indicator. To stop the process,
select ABORT (SOFT KEY 1).
6.
When the download is complete, the text "Parameter
download successful" will be displayed.
7.
The display will then return to the PAR BACKUP menu.
Select EXIT (SOFT KEY 1) to return to the main menu.
8.
The control panel can now be disconnected from the drive.
CLOCK SET MODE
Use the clock set mode to set the date and time for the internal
clock of the VFD. In order to use the timer functions of the VFD
control, the internal clock must be set. The date is used to deter-
mine weekdays and is visible in the fault logs.
To set the clock, perform the following procedure:
1.
Select MENU (SOFT KEY 2). The Main menu will be
displayed.
2.
Use the UP or DOWN keys to highlight CLOCK SET on
the display screen and press ENTER (SOFT KEY 2). The
clock set parameter list will be displayed.
3.
Use the UP or DOWN keys to highlight CLOCK VISI-
BILITY and press SEL (SOFT KEY 2). This parameter is
used to display or hide the clock on the screen. Use the UP
or DOWN keys to change the parameter setting. Press OK
(SOFT KEY 2) to save the configuration and return to the
Clock Set menu.
4.
Use the UP or DOWN keys to highlight SET TIME and
press SEL (SOFT KEY 2). Use the UP or DOWN keys to
change the hours and minutes. Press OK (SOFT KEY 2) to
save the configuration and return to the Clock Set menu.
5.
Use the UP or DOWN keys to highlight TIME FORMAT
and press SEL (SOFT KEY 2). Use the UP or DOWN
keys to change the parameter setting. Press OK (SOFT
KEY 2) to save the configuration and return to the Clock
Set menu.
6.
Use the UP or DOWN keys to highlight SET DATE and
press SEL (SOFT KEY 2). Use the UP or DOWN keys to
change the day, month, and year. Press OK (SOFT KEY 2)
to save the configuration and return to the Clock Set menu.
7.
Use the UP or DOWN keys to highlight DATE FORMAT
and press SEL (SOFT KEY 2). Use the UP or DOWN
keys to change the parameter setting. Press OK (SOFT
KEY 2) to save the configuration and return to the Clock
Set menu.
8.
Press EXIT (SOFT KEY 1) twice to return to the main menu.
I/O SETTINGS MODE
Use the I/O Settings mode to view and edit the I/O settings.
To configure the I/O settings, perform the following procedure:
1.
Select MENU (SOFT KEY 2). The Main menu will be
displayed.
2.
Use the UP or DOWN keys to highlight I/O SETTINGS
on the display screen and press ENTER (SOFT KEY 2).
The I/O Settings parameter list will be displayed.
3.
Use the UP or DOWN keys to highlight the desired I/O
setting and press SEL (SOFT KEY 2).
4.
Use the UP or DOWN keys to select the parameter to
view. Press OK (SOFT KEY 2).
5.
Use the UP or DOWN keys to change the parameter setting.
Press SAVE (SOFT KEY 2) to save the configuration. Press
CANCEL (SOFT KEY 1) to keep the previous value. Any
modifications that are not saved will not be changed.
6.
Press EXIT (SOFT KEY 1) twice to return to the main
menu.

ACH550/ACS320 VFD Diagnostics

The drive detects error situations and reports them using:
Green and red LEDs on the body of the drive (located un-
der the keypad)
Status LED on the control panel
Control panel display
The Fault Word and Alarm Word parameter bits (parame-
ters 0305 to 0309)
The form of the display depends on the severity of the error. The
user can specify the severity for many errors by directing the drive
to ignore the error situation, report the situation as an alarm, or re-
port the situation as a fault.
FAULTS (RED LED LIT)
The VFD signals that it has detected a severe error, or fault, by:
Enabling the red LED on the drive (LED is either steady or
flashing)
Setting an appropriate bit in a Fault Word parameter (0305
to 0307)
Overriding the control panel display with the display of a
fault code
Stopping the motor (if it was on)
ALARMS (GREEN LED FLASHING)
For less severe errors, called alarms, the diagnostic display is advi-
sory. For these situations, the drive is simply reporting that it had
detected something unusual. In these situations, the drive:
Flashes the green LED on the drive (does not apply to
alarms that arise from control panel operation errors)
Sets an appropriate bit in an Alarm Word parameter (0308
or 0309)
Overrides the control panel display with the display of an
alarm code and/or name
Alarm messages disappear from the control panel display after a
few seconds. The message returns periodically as long as the
alarm condition exists. See Table 34 for a list of alarm codes.

Correcting Faults

The recommended corrective action for faults is shown in the
Fault Codes Table 33. The VFD can also be reset to remove the
fault. If an external source for a start command is selected and is
active, the VFD may start immediately after fault reset.
To reset a fault indicated by a flashing red LED, turn off the power
for 5 minutes. To reset a fault indicated by a red LED (not flash-
ing), press RESET from the control panel or turn off the power for
5 minutes. Depending on the value of parameter 1604 (FAULT
RESET SELECT), digital input or serial communication could
also be used to reset the drive. When the fault has been corrected,
the motor can be started.

History

For reference, the last three fault codes are stored into parameters
0401, 0412, 0413. For the most recent fault (identified by parame-
ter 0401), the drive stores additional data (in parameters 0402 -
0411) to aid in troubleshooting a problem. For example, a parame-
ter 0404 stores the motor speed at the time of the fault. To clear the
fault history (all of Group 04, Fault History parameters), follow
these steps:
1.
In the control panel, Parameters mode, select parameter 0401.
2.
Press EDIT.
3.
Press the UP and DOWN buttons simultaneously.
4.
Press SAVE.
65