01_IM_D0X7205001-01_EN-2.fm Page 124 Friday, June 9, 2023 2:03 PM
4

Installation

CAUTION
CAUTION
Strictly comply with the following rules to prevent damage of the indoor units and human injury.
• Do not put a heavy article on the indoor unit or let a person get on it. (Even units are packaged)
• Carry in the indoor unit as it is packaged if possible. If carrying in the indoor unit unpacked by necessity, use buffering cloth or other material not to damage the unit.
• To move the indoor unit, hold the hooking brackets (4 positions) only.
• Do not apply force to the other parts (refrigerant pipe, drain pan, foamed parts, resin parts or other parts).
• Hanging bolt pitch of air intake chamber side is different (centre position), make sure not to make mistake to install the setting direction.
• Carry the package by two or more persons, and do not bundle it with plastic band at positions other than specified.
• To install vibration isolation material to hanging bolts, confirm that it does not increase the unit vibration.
 External dimensions
Screw hole for duct
mounting (N-M4)
100
Φ90 knockout hole
(For air taking-in air)
31-EN
Hanging bolt pitch A
Unit external dimension B
C (Outside)
Air filter
Electrical control box
– 124 –
Hanging bolt
25 or less
(Only the position of
an access cover.)
Access cover
173
155
85
Refrigerant pipe
35
connecting port
(Liquid side ΦD)
Drain pipe
connecting port
Refrigerant pipe
connecting port
(Gas side ΦE)
Wires
drawing-out port
37
(Unit: mm)
Model type
A
B
C
D
E
301
770
700
650
6.4
9.5
401
770
700
650
6.4
12.7
561
970
900
850
6.4
12.7
801
1170
1100
1050
9.5
15.9