For the table below:
•
Header is the main vent pipe into which
several vents connect
•
Vent Length is the distance from the end of
the header to the vent termination.
•
Maximum vent length starts at the end of the
header system.
•
Use 10 ft (3 m) as equivalent vent length for
90° elbows.
Table 15
Common Vent Maximum Equivalent Vent Length
Rinnai Common Vent System or Schedule 40 PVC/CPVC
Water Heater
Model
CX199i
(REU-N3237FFC-US)
CX160i
(REU-N2530FFC-US)
Demand Duo
H-Series with SENSEI CX Installation Instructions
Max
# Water
System
Heaters
BTU/HR
2
398,000
3
597,000
4
796,000
5
995,000
6
1,194,000
7
1,393,000
8
1,592,000
2
320,000
3
480,000
4
640,000
5
800,000
6
960,000
Figure 40
Header
HEADER DIAMETER
3 in.
3 in.
4 in.
Vent
Vent
Diameter
Diameter
65 ft
150 ft
65 ft
90 ft
150 ft
100 ft
65 ft
Vent length
4 in.
6 in.
6 in.
6 in.
Vent
Vent
Diameter
Diameter
150 ft
150 ft
70 ft
150 ft
150 ft
34