For the table below:
Header is the main vent pipe into which
several vents connect
Vent Length is the distance from the end of
the header to the vent termination.
Maximum vent length starts at the end of the
header system.
Use 10 ft (3 m) as equivalent vent length for
90° elbows.
Table 15
Common Vent Maximum Equivalent Vent Length
Rinnai Common Vent System or Schedule 40 PVC/CPVC
Water Heater
Model
CX199i
(REU-N3237FFC-US)
CX160i
(REU-N2530FFC-US)
Demand Duo
H-Series with SENSEI CX Installation Instructions
Max
# Water
System
Heaters
BTU/HR
2
398,000
3
597,000
4
796,000
5
995,000
6
1,194,000
7
1,393,000
8
1,592,000
2
320,000
3
480,000
4
640,000
5
800,000
6
960,000
Figure 40
Header
HEADER DIAMETER
3 in.
3 in.
4 in.
Vent
Vent
Diameter
Diameter
65 ft
150 ft
65 ft
90 ft
150 ft
100 ft
65 ft
Vent length
4 in.
6 in.
6 in.
6 in.
Vent
Vent
Diameter
Diameter
150 ft
150 ft
70 ft
150 ft
150 ft
34