Carrier 40MBFAQ Service Manual page 35

Floor console ductless system size 12k
Hide thumbs Also See for 40MBFAQ:
Table of Contents

Advertisement

40MBFAQ: Service Manual
Check Procedures
Temperature Sensor Check
1. Disconnect the temperature sensor from PCB.
2. Measure the resistance value of the sensor using a multi-meter.
3. Check the corresponding temperature sensor resistance value table (refer to "DISASSEMBLY INSTRUCTIONS" on page 39).
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
WARNING
WARNING
Be sure to turn off all power supplies or disconnect all wires to avoid
electric shock. Operate after compressor and coil have returned to
normal temperature in case of injury.