5
FUNCTIONAL DESCRIPTION
Main unit / SC-GU1-485
Designation
Power indicator (Green)
Lights up when the power is ON.
Communication indicator (Green)
Lights up during communication.
Upper communication
Blinks when communication error between PLC (Programmable Logic
error indicator (Red) (Note)
Controller) and Master or Master and Slave, or command error occurs.
Lower communication
Blinks when communication error between the main unit and
sensor amplifers occur.
error indicator (Red) (Note)
DIP switch for address
setting
bit No.
8 to 6
5 to 1
bit No.
DIP switch for
8
communication setting
7
6
5
4
3
2 to 1
Reset switch
Makes the setting change valid.
Terminal block connector
This is used when the upper controller or the main unit is mounted.
Note: In case the upper communication error indicator (red) and the lower communication error
indicator (red) are mixed, each indicator blinks alternatively.
6
CONNECTION WITH UPPER COMMUNICATION CABLE
Make sure that the power is off while wiring.
Be sure to use the specified communication cable.
The communication distance should be within the specification.
When the main units (SC-GU1-485) are connect-
ed to each other, max. 31 nodes can be connect-
ed. Wire them as shown in the right figure.
The wire process length should be 7mm.
7mm
Do not plate the wire connected to the terminal
block connector with solder etc., since the
connected wire may come off by loosening screws.
The tightening torque of the screws for wire
fixing should be 0.5N m or less.
The screws of the flange part should be tighten
as well so that the terminal block connector
does not come off from the main body. The
tightening torque should be 0.5N m or less
For the communication cable, use a shielded
twist-pair cable. Furthermore, the shield should
be connect to the frame ground (F.G.).
<Recommended>
KPEV-S 0.5SQ 1P manufactured by Sumitomo Electric
Industries, Ltd.
Note that the frame ground (F.G.) terminal has
not been connected to inside the unit.
Be sure that the DIP switch/termination select
on the main unit in the termination node is set
to ON side, and the DIP switch/termination
select on the main units other than the
termination node is set to OFF side.
Connect a termination resistance (100 ) in
the termination node.
Note: The termination resistance is fit in the main unit.
Be sure that the DIP switch/termination select on the main unit in the termination node is set
to ON side, and the DIP switch/termination select on the main units other than the termination
node is set to OFF side.
Description
8
7 6 5
4
3
2
1
bit No.
(
This figure shows the
factory setting.
Name
Description
Not used.
Address setting
They are used for address setting.
8
7 6 5
4
3
2
1
bit No.
This figure shows the
(
factory setting.
Name
Description (0: OFF, 1: ON)
0:
, 1: Termination
Be sure to set the DIP switch
on
the
main
unit
Termination
termination node to ON.
change
Be sure to set the DIP switch
on the main units other than the
termination node to OFF.
BCC check
0: Invalid, 1: Valid
Stop bit
0: 1bit, 1: 2 bit
0: Invalid, 1: Valid
Parity check
0: Even number, 1: Odd number
Data length
0: 7 bit, 1: 8 bit
Communication
00: 9.6kbps, 01: 19.2kbps
speed
10: 38.4kbps, 11: 57.6kbps
To upper controller
A
B
F.G.
A
B
<1st node>
A
B
F.G.
A
B
<2nd node>
A
B
F.G.
A
B
<Termination node>
<DIP switch for communication setting>
Termina-
tion select
Only the main unit of the
termination node is ON.
7
HOW TO CHANGE THE LENGTH OF LINK CABLE (SC-GU1-CC02)
The link cable (SC-GU1-CC02) can be shortened with the
desired length. However, the cable cannot be extended.
Procedure
Use a flathead screwdriver (Blade width: 2mm or less) to push
the operating lever (white) located at the wire inlet on the main
unit side connector of the link cable until it is locked.
Cut the link cable at the desired length.
Process the core length to 7 to 8mm in accordance with 'STRIP GAUGE' indicated
on the side of the connector, and twist the core
several times.
When using shielded wires, be sure to twist
the wire to a diameter of
I
nsert the wire to the bottom of the wire inlet.
Check that the shielded part of the wire is
properly inserted into the wire inlet as well
as that the core end has passed through
the wire connection area as shown in the
right figure.
(
<Connector pin arrangement>
Place the head of a flathead screwdriver
underneath the operating lever (white)
(
through the releasing slot, and lift the
screwdriver head.
If you hear a snap, the operating lever
(white) is returned and the wire is fixed.
at
the
Slightly pull the wire to ensure that the wire
is not loose.
Also, check that they are not in contact with
each other.
Fit the cover to the connector.
8
SETTING
Follow the procedure given below for setting.
Procedure
Mount this product and carry out wiring.
Carry out the address setting by using the DIP switch for address setting.
Carry out the communication-related setting by using the DIP switch for
communication setting.
Turn the power on.
Note: When the setting is changed after the power was turned on, be sure to press the reset switch.
For communication conditions and commands, refer to 'Product specification'
and 'Communication command specification'.
9
CAUTIONS
This product has been developed / produced for industrial use only.
Make sure that the power supply is off while wiring and adding the units.
Take care that wrong wiring will damage the sensor.
Verify that the supply voltage variation is within the rating including the
sensor amplifer.
In case noise generating equipment (switching regulator, inverter motor,
etc.) is used in the vicinity of this product, connect the frame ground (F.G.)
terminal of the equipment to an actual ground.
Do not use during the initial transient time (1 sec.) after the power supply is switched on.
This sensor is suitable for indoor use only.
Do not use this sensor in places having excessive vapor, dust, etc.
Take care that the product does not come in contact with water, oil, grease,
organic solvents, such as, thinner, etc., or strong acid and alkaline.
This sensor cannot be used in an environment containing inflammable or explosive gases.
Never disassemble or modify the sensor.
Panasonic Industry Co., Ltd.
Panasonic Industrial Devices SUNX Co., Ltd.
https://panasonic.net/id/pidsx/global
Please visit our website for inquiries and about our sales network.
Panasonic Industrial Devices SUNX Co., Ltd. 202
, 202
1.2mm or less.
Core wire
Shielded wire
Not connected
Not connected
STRIP GAUGE
Wire
Connector
Core length:
7 to 8mm
Shielded part
Wire
of wire
connection
area
Wire inlet
Operating lever (white)
Releasing slot
Shielded wire
PRINTED IN JAPAN