Combustion Air Conversions - Trane A801X040AM3SDA/B Installation, Operation And Maintenance Manual

Upflow/downflow/horizontal left/right gas-fired, single stage induced draft furnaces with high efficiency motor
Table of Contents

Advertisement

F F u u r r n n a a c c e e C C o o m m b b u u s s t t i i o o n n A A i i r r E E x x h h a a u u s s t t O O p p t t i i o o n n s s

Combustion Air Conversions

Important: After deciding the orientation of the flue outlet, cut the
metal tabs around the appropriate 5" metal cutout on the
furnace cabinet and remove the cutout, if necessary.
Note: When rotating the inducer it may be necessary to cut the wire
tie. A new wire tie must be installed once the inducer is rotated.
Note: Self-tapping screws are recommended for attaching the vent pipe to the inducer outlet (applicable to all the instructions below).
Upflow orientation with top venting
Refer to
Upflow orientation with right side venting
Refer
Horizontal left orientation with top venting
Refer
42
Step 1.
Step 2.
to
Step 6.
Step 2.
to
Step 6.
Pressure Switch locations
A801X: PS is connected to the hot header. Disregard pressure switch
tubing connected to the inducer. Not applicable on single stage
furnaces.
Upflow orientation with left side venting
Note: When rotating the inducer it may be necessary to cut the wire
tie. A new wire tie must be installed once the inducer is rotated.
Refer
Step 2.
Horizontal left orientation with left side venting
Refer to
Horizontal right orientation with right side venting
Refer to
to
Step 6.
Step 9.
Step 9.
A801X-SVX001-1C-EN