IEEE 1613 Type Tests
Note
Dielectric Strength
Environmental Type Tests
Note
Class 2 refers to Measuring relays and protection equipment for which a very
high security margin is required or where the vibration levels are very high, (e.g.
shipboard application and for severe transportation conditions).
IEC 60068-2-1
IEC 60068-2-2
RUGGEDCOM M969
Equipment Manual, 10/2023, C79000-G8976-1039-05
Test
If the unit contains copper ports, the IEEE 1613 conformance is Class 1 (during
disturbance, errors may occur but recovery is automatic).
If the unit contains all fiber ports, the IEEE 1613 conformance is Class 2 (during
disturbance, no errors will occur).
Description
ESD
Enclosure Contact
Radiated RFI
Fast Transient
Earth ground ports
Oscillatory
HV Impulse
Test
Cold Temperature
Dry Heat
7.3 EMC and Environmental Type Tests
Description
AC Power ports
Enclosure Air
Enclosure ports
Signal ports
DC Power ports
AC Power ports
Signal ports
DC Power ports
2.5 kV common & differential mode @ 1MHz
AC Power ports
2.5 kV common & differential mode @ 1MHz
Signal ports
DC Power ports
AC Power ports
Signal ports
DC Power ports
AC Power ports
Description
Test Ad
Test Bd
Test Levels
5 kV
Test Levels
± 8 kV
± 15 kV
35 V/m
± 4 kV @ 2.5 kHz
± 4 kV
± 4 kV
± 4 kV
2.5 kV common mode @ 1MHz
5 kV (Failsafe Relay)
5 kV
5 kV
2 kV
1.5 kV
2 kV
Test Levels
Severity Levels
-40 °C (40
°F), 16 Hours
85 °C (185
°F), 16 Hours
Certification
Severity
Levels
47