Lindab Atrium Plana Series Installation Instructions Manual

Radiant cooling- and heating panel
Hide thumbs Also See for Atrium Plana Series:
Table of Contents

Advertisement

Quick Links

l i n da b | f o r a b et t er cl i m at e
LindabAtrium Plana
Radiant cooling- and heating panels
Installation instructions
© 2023.11 Lindab Ventilation. All forms of reproduction without written permission are forbidden.
is the registered trademark of Lindab AB.
Lindab's products, systems, product and product group designations are protected by intellectual property rights (IPR).

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Atrium Plana Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Lindab Atrium Plana Series

  • Page 1 Radiant cooling- and heating panels Installation instructions © 2023.11 Lindab Ventilation. All forms of reproduction without written permission are forbidden. is the registered trademark of Lindab AB. Lindab's products, systems, product and product group designations are protected by intellectual property rights (IPR).
  • Page 2: Table Of Contents

    4.1.5 Possible connections water cooling or heating (2-pipe, standard)..........13 4.1.6 Possible connections water cooling and heating (4-pipe, standard) ........13 4.1.7 Water pipe dimensions and placement..... 13 Lindab reserves the right to make changes without prior notice 2023-11-10...
  • Page 3: Symbols

    See also the separate document “Accessories." Lindab will also provide you with a full ventilation system, with a wide range of Lindab Safe components. See also “Air Duct Systems." Do not place the product directly on the floor. Use the pro- 2.2 Safe operation...
  • Page 4: Tools

    Please remember to remove plastic folio and other protection material before commissioning and clean the product before hand over. Lindab reserves the right to make changes without prior notice 2023-11-10...
  • Page 5: Packing, Unpacking Guideline

    | fo r a b e t te r c l i ma te Installation instruction Atrium Plana 2.10 Packing, unpacking guideline Never use water pipe connections for lifting 14-60 kg ! Lindab reserves the right to make changes without prior notice 2023-11-10...
  • Page 6: Product Labelling

    • Production order: Production order no. • Goods mark: Marking noted on order • Product ID: Product number • Sign: To be signed when checked and commissioned on site Lindab reserves the right to make changes without prior notice 2023-11-10...
  • Page 7: Contents Of Order

    Go to 5.4 "Preparation for installation on the product" for more details. Order no: See Accessories. 2.17.2 Flexible hoses Order no: See Accessories. 2.17.3 Transformer Order no: See Transformers. 2.17.4 Tectite fittings Accessories. Lindab reserves the right to make changes without prior notice 2023-11-10...
  • Page 8: Product Specification

    3. Product specification The Lindab Atrium Plana is a simple yet powerfull radiant panel, with an uncomlicated design that ensures that the Atrium Plana does not draw attention on the building and interior design. The water pipes are made of copper. Nevertheless, water should be oxygen-free to prevent corrosion.
  • Page 9: Type Hc-Ocmbined Heating And Cooling

    PN10 Type HC- combined heating and cooling panel, specific measures and other data - *HW: Hot Water. Tolerances for deflection: 2 mm deflection per 1 m off panel length/width. Lindab reserves the right to make changes without prior notice 2023-11-10...
  • Page 10: General Structure

    2003, EN-14037-2: 2016 and EN-14037-5: 2016 at accredited to EN ISO/ IEC 17025 notified body by DIBt according to (EU) No. 305/2011 NB 1428, WSPlab, Stuttgart, Germany and are CE-marked. Lindab reserves the right to make changes without prior notice 2023-11-10...
  • Page 11: Connections

    When connecting a panel or a beam with the piping system either a push-on fitting or a compression coupling should be used. Lindab have tested and recommends John Guest push on fittings as well as push-on fittings from Tectite (available as accessory.
  • Page 12: Push-On Valve

    • Please refer to the suppliers manual. = 70 mm (to ensure you can open the couplings again). Lindab flexible hoses are available with straight end (male) for direct connection to Lindab valves also. Lindab reserves the right to make changes without prior notice...
  • Page 13: Possible Connections Water Cooling Or Heating (2-Pipe, Standard)

    All water pipe connections are Ø = 10 mm. Connect water with push-on or compression couplings or similar. Use the support sleeves. Do not solder! (see chapter 4.) Type C/H CU-Ø10x0.5 CU-Ø10x0.8 Type HC Lindab reserves the right to make changes without prior notice 2023-11-10...
  • Page 14: Installation Of Product

    For the handling of the product please refer to 2.5. 5.2 Adaption to ceiling systems 5.2.1 Ceiling systems Atrium Plana is ready for ceiling sytem 1 only, for others please contact local Lindab contact for further explanation/support. T24/T15 lay-in 600 ( I-60 ) Water...
  • Page 15: General Installation Principles

    1 pc, 540-1000 mm (order no. 646742) 1 pc, 1750-2000 mm (order no. 653454) 1. 4 pcs for L < 2.4 m 2. 6 pcs for L ≥ 2.4 m Lindab reserves the right to make changes without prior notice 2023-11-10...
  • Page 16: Mounting Accessories Pendulum + Suspension Hook

    5.4.3 Mounting accessories – Wiring hanger system Please check local Lindab branches for regional assortment. 1. 4 pcs for L < 2.4 m 2. 6 pcs for L ≥ 2.4 m Lindab reserves the right to make changes without prior notice 2023-11-10...
  • Page 17: Mounting Accessories - Threaded Rod M6 + Suspension Hook

    1. 4 pcs for L < 2.4 m 2. 6 pcs for L ≥ 2.4 m The ceiling clips are not included in the delivery and can be orde- red as separate accessories. Lindab reserves the right to make changes without prior notice 2023-11-10...
  • Page 18: Mounting Direct To Concrete

    1 pc, Atrium Plana (order no. 167673) 1 pc, Atrium Plana (order no. 167672) x2 (x3) 1. 4 pcs for L < 2.4 m 2. 6 pcs for L ≥ 2.4 m Lindab reserves the right to make changes without prior notice 2023-11-10...
  • Page 19: Adjustment And Commissioning

    A hydraulic balance is obvious to ensure that all the beams (panels or facade units) in the system will always be supplied with their required (planned) water flow rates. Lindab refers to the proportional method, where all beams (panels or facade units) are balanced to the same proportion of the requested water flow rate.
  • Page 20 We at Lindab have therefore made it our most important objective to contribute to an indoor climate that improves people’s lives. We do this by developing energy-efficient ventilation solutions and durable building products.