Download Print this page

Timer Settings - CAMDEN EXACT CX-DA400 Installation Instructions Manual

Door prop alarm

Advertisement

• SHUNT RECYCLE (see description below)
A) Jumper 5 is ON
B) Jumper 5 is OFF
SHUNT RECYCLE EXPLAINED -
When Shunt Recycle is Enabled (ON), a Shunt Contact or Voltage Sense Input
during the Alarm Delay warning period (beeping) will reset the Silent Time
Timer. Shunt Recycle gives the User the ability to Hold the door indefinitely by
repeating a valid input during each Alarm Delay warning.
When disabled, only a Key or Bypass input will reset the DMA.
4

TIMER SETTINGS

• The SHUNT DELAY TIMER begins after a Valid User input (prior to
door being opened) and if door is not opened the DMA will reset
when timer expires. Cancels upon door opening.
A) Shunt Delay works only with Intrusion Detection enabled.
B) See table on Back Plate for Jumper 7&8 setting detail.
SHUNT INPUT
EXPLAINED - This
input from a PIR
or Access Control
system provides
user validation.
SEE TABLE ON REVERSE
CX-DA400 Door Prop Alarm Installation Instructions
• SILENT TIME SELECT begins when the door is opened
by a valid user. (see Timer Setting Table on reverse)
A) Timer has two ranges selected with Jumper 9;
• Normal - 0 seconds to 2.5 minutes (Jumper OFF)
• Extended - 3 minutes to 90 minutes (Jumper ON)
B) After selecting appropriate range, turn dial to SET #
for the Silent Time period desired for your application.
• ALARM DELAY SELECT begins on the expiration of the
Silent Timer. Warning Alarm sounds locally to alert user.
A) Turn dial to SET # on table (see reverse) for the time
you want the Warning (beeping) alarm to sound (prior to triggering
the Door Prop Alarm Horn and Relay).
• AUTO RESET TIME SELECT is the minimum time the
Horn, LED and Relays are on following an alarm condition.
NOTE: Alarm will continue for as long as the door is open
A) Turn the dial to SET Timer (0 seconds to 5 minutes,
or Manual).
5
POWER
• POWER - Connect 12-24 VAC/DC to TS1 11&12.
Not polarity sensitive.
6
OUTPUTS (FORM-C)
• DOOR STATUS RELAY
TS2-22,23,24 changes state when the
Door Input changes. Used to monitor
changes in Door Contact status.
• DOOR PROP ALARM RELAY
TS2-19,20,21 changes state when a
door is held open beyond the Silent and
Alarm Delay time, combined.
• FORCED DOOR/TAMPER ALARM
RELAY
TS2-16,17,18 changes state when a
door is forced or a tamper condition
exists (Door Supervision/Tamper
Switch).
• BYPASS/KEY SWITCH
STATUS RELAY
TS2-13,14,15 changes state during Bypass (TS1 9&10) and Key
Switch Inputs. Used to monitor for changes in Bypass status.
Page 4 of 6

Advertisement

loading