Download Print this page

Philips dynalite DRC1220FR-GL-ENC Installation Instructions Manual page 8

Wired systems

Advertisement

Device wiring
0/1-10 V / DALI Controllers
DDBC1200
Control Channel Ratings
≤ 80/CH
DALI
Broad-
Guaranteed 160 mA
cast
Maximum 250 mA
Insulation: basic
≤ 80/CH
DSI
Sink 50 mA
0-10 V
Source 50 mA
DDBC516FR
Output Ratings/Channel (CH)
Load Type
General Use
Incandescent
Standard Driver
Electronic Driver
Motor
M
Pilot Duty
Control Channel Ratings
≤ 10/CH
DALI
Address-
Guaranteed 20 mA
able and
Maximum 250 mA
Broadcast
Insulation: basic
≤ 10/CH
DSI
1-10 V
Sink 10 mA
Source 10 mA
8 | Preassembled DIN Rail Cabinets (UL)
≤ 300
≤ 300
Driver
dependent
CH1-CH5
16 A, 277 V
16 FLA (1 HP), 120 V
14.5 FLA (2
/
HP), 240 V
1
2
14.1 FLA (3 HP), 277 V
6 A, 120 V
3 A, 240 V
2.6 A, 277 V
100-240 V
0.15 mA
≤ 50
≤ 50
Driver
dependent
100-240 V
0.5 A
DA-
DA+
DA-
DA+
DA-
DA+
DA-
DA+
N
L
CH1
CH2
CH3
CH4
SUPPLY:
100-240V ~ 50/60Hz 0.5A max.
DDBC1200
OUTPUT:
12 x DALI Broadcast / 0-10V / DSI
Class 1 or Class 2 (UL)
DALI:
14V 160mA nom. 250mA max. per channel
BALLAST CONTROLLER
Refer to manual for DALI load ratings
1
2
3
4
5
WARNING: MANUAL OVERRIDES DO NOT PROVIDE ISOLATION
GND
AUX
< 65 ft
(20 m)
1
/ 3
CH-CH ≤ 300 V
(UL) / 400 V
5.56 Lb-in
0.6 Nm
10+ AWG
≤ 5 mm
2
IN OUT
IN OUT
N
L
CH1
CH2
DDBC516FR
SIGNAL DIMMER CONTROLLER
SUPPLY: 100-240V~, 0.15A
ON
OUTPUT: 5 x Switched Output
1
Refer to load table below
5 x DALI / DSI / 1-10 V
OFF
1-10V: 10mA source / 10mA sink per channel
DALI/DSI: 20mA guaranteed, 250mA max
WARNING:
Insulation system: Basic
DyNet:
12V , 120mA, SELV/Class 2 (UL)
WARNING:
t
:
0° to 40°C (32° to 104°F)
a
TO DE-ENERGIZE THE DEVICE FOR SERVICING
Made in Australia. Signify, IBRS 10461, 5600 VB, NL
Copper conductors only, 75°C minimum
For Control of Electronic Ballast, CFLs, LED, and LED Lamps
CAN-ICES-003(B)/NMB-003(B)
GND
UL924
< 65 ft
(20 m)
10+ AWG
≤ 5 mm
DA-
DA+
DA-
DA+
DA-
DA+
DA-
DA+
DA-
DA+
DA-
DA+
CH5
CH6
CH7
CH8
CH9
CH10
DALI INSULATION SYSTEM: Basic
SERVICE LED SIGNAL MODES:
SERVICE SWITCH:
0-10V: 50mA source / 50mA sink max. per channel
OK
1 PUSH = NETWORK SIGN ON
t
a: 0° to 40°C (32° to 104°F)
OK, NETWORK BUSY
3 PUSHES = ALL CHANNELS 100%
Made in Australia
FAULT
4 PUSHES = INITIALISE DALI DRIVERS
Signify, IBRS 10461, 5600 VB, NL
PUSH & HOLD FOR 4 SEC = RESET
6
7
8
9
10
11
DyNet
SELV/Class 2
RS-485 DyNet/DMX512 Rx
SELV/Class 2 (UL)
12 V
200 mA
(CE)
DALI DSI 1-10 V
IN OUT
IN OUT
IN OUT
DA- DA+
DA- DA-
DALI 1 DALI 2
CH3
CH4
CH5
DALI - FELV/Class 1 or Class 2 (UL)
SERVICE SWITCH:
1 PUSH = NETWORK
ON
3 PUSHES = ALL CHANNELS 100%
2
3
4
5
4 PUSHES = OUTPUT TEST MODE &
INITIALISE DALI BALLASTS
OFF
PUSH & HOLD FOR 4 SEC = RESET
SERVICE LED SIGNAL MODES:
MANUAL OVERRIDES DOES NOT PROVIDE PERMANENT ISOLATION
MORE THAN ONE DISCONNECT SWITCH MAY BE REQUIRED
.
DyNet
SELV / Class 2 (UL)
SHLD GND D+ D- +12V UL924
RJ12
RS-485 DyNet/DMX512 Rx
SELV/Class 2 (UL)
12 V
200 mA
To connect to RS-485, plug RJ45
connectors into the included
DINGUS-PDRAS-RJ45-TRIPLE.
5.5 Lb-in
2
0.6 Nm
DA-
DA+
DA-
DA+
CH11
CH12
12
4EE5
RJ12
RJ12
4.4 Lb-in
0.5 Nm
12+ AWG
SUPPLY
≤2.5 mm
2
N
L
ON
DA- DA+
DA- DA+
DA- DA+
DALI 3
DALI 4
DALI 5
1
OFF
SIGN-ON
4EE5
OK
OK, NETWORK BUSY
FAULT
SERVICE
RJ12
SWITCH

Advertisement