Table of faults
Table 11- List of faults
Fault
Fault
code
A01
No burner ignition
Flame present signal with
A02
burner off
F05
Fan fault
No flame after the ignition
A06
phase
EN
Possible cause
No gas
Ignition/detection elec-
trode fault
Insufficient gas supply
pressure
Trap blocked
Air/fume ducts obstructed
Wrong calibration
Faulty gas valve
Electrode fault
Card fault
No 230V power supply
Tachometric signal inter-
rupted
Fan damaged
Ionization electrode fault
Flame unstable
air/fume ducts obstructed
Trap blocked
Wrong calibration
Insufficient gas supply
pressure
cod. 3541V304 - Rev. 00 - 03/2024
Cure
Check the regular gas flow to the boiler
and that the air has been eliminated
from the pipes
Check the wiring of the electrode and
that it is correctly positioned and free of
any deposits; replace the electrode if
necessary.
Check the gas supply pressure
Check the trap and clean it if neces-
sary
Remove the obstruction from the flue,
fume extraction ducts, air inlet and ter-
minals.
Do the Calibration procedure [AUTO
SETUP].
Check the gas valve and replace it if
necessary
Check the ionization electrode wiring
Check the condition of the electrode
Electrode to ground
Cable to ground
Check the trap and clean it if neces-
sary
Check the card
Check the 5-pin connector wiring
Check the fan and replace it if neces-
sary
Check the position of the ionization
electrode, free it from any encrusta-
tions and do the Calibration procedure
[AUTO SETUP]. Replace the electrode
if necessary.
Check the burner
Remove the obstruction from the flue,
fume extraction ducts, air inlet and ter-
minals
Check the trap and clean it if neces-
sary
Do the Calibration procedure [AUTO
SETUP].
Check the gas supply pressure
375