Troubleshooting - heat-timer TRV Installation And Operation Manual

Wireless transceiver for platinum controls with communication
Table of Contents

Advertisement

Symptom
Status LEDs are not lighting.
Both status LEDs are continuously 
blinking.
No sensor communications.
Heat‐Timer Corp.

Troubleshooting

Possible Cause
No power to the TRV.
System ID has not been configured.
Poor wireless signal strength.
Troubleshooting          13
Recommended Action(s)
Verify the TRV is receiving power (AC transformer 
or DC adapter) and all power cables are in good 
condition and are connected.
Refer to:
• "Mounting the Wireless TRV" on page 8
• "Power Input Wiring" on page 9
Configure the System ID. If the LEDs are still 
blinking after the System ID has been configured, 
contact Customer Support.
Refer to "Programming the Wireless TRV System 
ID" on page 5.
Check the Wireless TRV RSSI LEDs (Figure 1 on 
page 3). At least three LEDs should be lit, indicating 
"good" signal strength.
If fewer than three RSSI LEDs are lit, check to 
ensure the antenna connection is secure and that 
the antenna is undamaged.
If necessary, remove the source of RF interference 
or relocate the Wireless TRV.
Refer to:
• "Attaching an External Antenna" on page 10
• "Mounting the Wireless TRV" on page 8