F6
Outdoor DC fan
failure
E0
Inlet water temp
sensor failure
E1
Outlet
sensor failure
E2
After
throttling
temp
sensor
failure
E3
Air suction temp
sensor failure
E4
Outdoor coil temp
sensor failure
E5
Outdoor
environment temp
sensor failure
E6
Exhaust
sensor failure
E7
EVI return circuit
air return temp
sensor failure
E8
High
pressure
sensor failure
E9
Low
pressure
sensor failure
EA
Economizer inlet
temp
sensor
failure
EB
Indoor
environment temp
sensor failure
EC
Economizer outlet
temp sensor
failure
ED
Buffer tank sensor
Driving of DC fan is failure
The cable of the sensor
open
temp
or shout circuit
The probe of the sensor fall
off
the sensor short circuit
temp
Reconnect the cable of the sensor
Retighten the probe
Repair or replace the cable
Replace PCB
-
-