Condensate drainage connector
3
shockproof rubber pads
2.7.2 Design of the store tank in the system
1 - kW is the unit for cooling capacity, L is the unit for (G) minimum water flow volume in the
formula. Comfortable type air conditioner
G= cooling capacity×2.6L
Process type cooling
G= cooling capacity×7.4L
2 - In certain occasion (especially in manufacture cooling process), for conforming the
system water content requirement, it's necessary to mount a tank equipping with a cut-off
baffle at the system to avoid water short-circuit, Please see the following schemes:
Minimum and maximum water flow rates:
Ethylene glycol solutions
Water and ethylene glycol solutions used as a thermal vector in the place of water
reduce the performance values given in the following table.
During winter leaving the unit unused, please drain water out completely from unit if
no antifreeze were charged into pipeline, or keep power on (at standby or off
status) and ensure that water is contained inside of unit.