Ww Electrical Data W/Powered Convenience Outlet - High Static Drive Motor - York WW-15 Installation Manual

Gas/electric single package air conditioners
Table of Contents

Advertisement

175244-BIM-A-0706
TABLE 12: WW ELECTRICAL DATA W/POWERED CONVENIENCE OUTLET - HIGH STATIC DRIVE MOTOR
COMPRESSORS
MODEL
(TON-
VOLTAGE
RLA
NAGE)
EACH
208
22.4
230
22.4
-15
(15)
460
10.9
575
8.3
208
30.1
230
30.1
-20
(20)
460
15.5
575
12.1
NOTE 1: HACR Type per NEC.
Unitary Products Group
ID
OD FAN
BLOWER
MOTORS
LRA
MOTOR
FLA EACH
EACH
FLA
164
2.1
20.0
164
2.1
20.0
100
1.2
10.0
78
0.9
7.5
225
2.4
24.2
225
2.4
24.2
114
0.9
12.1
80
0.6
10.3
HEATER OPTION
CONV
OUTLET
MODEL
KW
STAGES
AMPS
None
0.0
E18
13.5
10.0
E36
27.0
E54
40.6
E72
54.1
None
0.0
E18
18.0
10.0
E36
36.0
E54
54.0
E72
72.0
None
0.0
E18
18.0
5.0
E36
36.0
E54
54.0
E72
72.0
None
0.0
E18
18.0
4.0
E36
36.0
E54
54.0
E72
72.0
None
0.0
E18
13.5
10.0
E36
27.0
E54
40.6
E72
54.1
None
0.0
E18
18.0
10.0
E36
36.0
E54
54.0
E72
72.0
None
0.0
E18
18.0
5.0
E36
36.0
E54
54.0
E72
72.0
None
0.0
E18
18.0
4.0
E36
36.0
E54
54.0
E72
72.0
MIN.
CIRCUIT
AMPACITY
AMPS
(AMPS)
~
~
88.8
1
37.5
88.8
2
74.9
131.2
2
112.7
178.4
2
150.2
187.7
~
~
88.8
1
43.3
91.6
2
86.6
145.8
2
129.9
167.4
2
173.2
210.7
~
~
44.3
1
21.7
45.8
2
43.3
72.9
2
65.0
83.7
2
86.6
105.4
~
~
33.8
1
17.3
36.0
2
34.6
57.7
2
52.0
66.3
2
69.3
83.7
~
~
111.5
1
37.5
111.5
2
74.9
136.4
2
112.7
183.6
2
150.2
192.9
~
~
111.5
1
43.3
111.5
2
86.6
151.0
2
129.9
172.7
2
173.2
216.0
~
~
55.6
1
21.7
55.6
2
43.3
75.5
2
65.0
86.3
2
86.6
108.0
~
~
43.9
1
17.3
43.9
2
34.6
61.2
2
52.0
69.8
2
69.3
87.2
MAX.
FUSE/
1
BRKR
SIZE
(AMPS)
110
110
150
200
200
110
110
150
175
225
50
50
80
90
110
40
40
60
70
90
125
125
150
200
200
125
125
175
175
225
70
70
80
90
110
50
50
70
70
90
29

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ww-20Ww-25

Table of Contents