Connect Condensate Drain - Carrier 48XP024 Installation Instructions Manual

Hide thumbs Also See for 48XP024:
Table of Contents

Advertisement

y
CORNER WEIGHTS (SMALL CABINET)
Unit
024
Total Weight
350
Corner Weight 1
70
Corner Weight 2
54
Corner Weight 3
84
Corner Weight 4
141
UNIT 48XP
024
030
036
042
048
060
WARNING
!
PERSONAL INJURY HAZARD
Failure to follow this warning could result in personal
injury/death.
Accessory lifting kit is only to be used with Small Packaged
units which have a composite unit base with molded rigging
holds.
1
4
030
036
350
388
70
78
54
60
84
94
141
156
Fig. 5 - - 48XP Corner Weights
A
914-1371
(36"-54")
927.57
B
(36"-52")
1226.3
(48.28")
PLACE RIGGING STRAPS IN
BASEPAN SLOT (BELOW HANDHOLDS)
BEFORE RIGGING
MAXIMUM SHIPPING WEIGHT
lb
kg
372
169
372
169
410
186
462
210
485
220
521
236
Fig. 6 - - Suggested Rigging
x
CORNER WEIGHTS (LARGE CABINET)
Unit
042
Total Weight
440
Corner Weight 1
88
Corner Weight 2
68
Corner Weight 3
106
Corner Weight 4
177
DUCTS
SEAL STRIP MUST BE IN
PLACE BEFORE PLACING
UNIT ON ROOF CURB
A
in.
mm
22.0
558.5
22.0
558.5
22.0
558.5
20.0
508.0
21.5
546.1
23.5
596.9
Step 6 — Connect Condensate Drain
NOTE: When installing condensate drain connection be sure to
comply with local codes and restrictions.
Model 48XP disposes of condensate water through a 3/4 in. NPT
fitting which exits through the compressor access panel (See Fig.
2 and 3 for location).
Condensate water can be drained directly onto the roof in rooftop
installations (where permitted) or onto a gravel apron in
groundlevel installations. Install a field- -supplied condensate trap
at end of condensate connection to ensure proper drainage. Make
sure that the outlet of the trap is at least 1 in. lower than the
6
2
3
C00070
048
060
463
499
92
100
72
78
111
120
188
201
C99015
B
in.
mm
14.50
368.3
14.50
368.3
15.30
388.6
21.25
539.8
16.3
414.0
16.3
414.3