Vane Pass defect: enable or disable Vane Pass defect function. Can set the
number of vane once user enable this function
Vibration alarm and range:
–
Peak: warning limit setting on peak value
–
Peak to Peak: warning limit setting on peak to peak value
–
Crest factor: warning limit setting on crest factor value
–
Power in band: warning limit setting on power in band value, user can set the
frequency detection by 2 modes, which are Order and Band.
a. Order: calculate the frequency range by order and bandwidth. Ex: order 2
and bandwidth 0.5 means to detect the range between (main RPM * 2)
±(main RPM * 0.5)
b. Band: frequency: set the exactly frequency range directly.
Vibration alarm and range: warning limit and error setting of temperature value.
11
WISE-2460P User Manual