Advertisement

5.0.

INSTALLING THE OUTDOOR UNIT

WARNING
Installation must be performed by suitably qualified professionals only.
5.1.
Handling
After removing the packaging, check that the contents are intact and complete.
The outdoor unit must always be kept upright.
Handling must be done by suitably equipped qualified personnel using equipment that is for
suitable the weight of the appliance.
5.2.
Location
Use bolts to secure the unit to a flat, solid base. When mounting the unit on a wall or the roof, make
sure the support is firmly secured so that it cannot move in the event of intense vibrations or a
strong wind.
Do not install the outdoor unit in pits or air vents.
5.3.
Installing the Refrigerant Pipes
Use suitable connecting pipes and equipment for the refrigerant R410A.
Table 5: Refrigerant Pipe Connection Data
Model
Maximum Number
Number
of Indoor Units
Connected
LNMT054V4
LNMT073V4
LNMT082V4
12
Maximum
Connection Pipe
Length (m)
2
3
4
LENNOX MULTI SPLIT INVERTER
Maximum
Connection Pipe
Length (Single
Indoor Unit) (m)
20
60
70
Outdoor Unit
Maximum Height
of Refrigerant Pipe
10
20
20
13 23 50
|
lennoxaus.com.au
(m)
5
10
10