July 2016
Specifications
The Flame Simulator Kit, Part No. 00975-9000-0010 includes the FS-UVIR-975 flame simulator, battery, charger and user guide
in carrying case.
Table 1 - FS-UVIR-975 Flame Simulator
Simulator Models
Detector Types
975UR
975UF
General Specifications
Temperature range
Vibration protection
Activations between charges
Electrical Specifications
Power
Maximum current
Battery capacity
Charging time
Mechanical Specifications
Dimensions
Weight
Enclosure
Explosion-proof enclosure
Water and dust tight
EmersonProcess.com/FlameGasDetection
Detector Sensitivity Setting
50 ft (15 m)
60 ft (20 m)
32 °F to +122 °F (0 °C to +50 °C)
1 g (10–50 Hz)
100 max.
14.8 V (4 x 3.7 V rechargeable lithium-ion battery)
4 A
2.2 AH
2 hr at 2 A
9 x 7.3 x 5.35 in (230 x 185 x 136 mm)
5.5 lb (2.5 kg)
Aluminum, heavy-duty copper-free, black zinc coating
ATEX and IECEx approved
Ex II 2 G D
Ex d ib op is IIB + H2 T5 Gb
Ex ib tb IIIC T135 °C Db
-20 °C to +50 °C (-4 °F to +122 °F)
IP65
FS-UVIR-975 Flame Simulator
Min. Testing Distance
2.5 ft (0.75 m)
2.5 ft (0.75 m)
Max. Testing Distance
8 ft (2.5 m)
23 ft (7 m)