Detection Ranges Per Detector / Flame Simulator - Emerson Rosemount FS-UVIR-975 Instruction Manual

Flame simulator for rosemount 975uf and 975ur
Hide thumbs Also See for Rosemount FS-UVIR-975:
Table of Contents

Advertisement

Operation Instructions
CAUTION!
The following test simulates a real fire condition and may activate the extinguishing system or
other alarms. If this is not desired, disconnect/inhibit them before the test and reconnect after
the simulation.
Procedure
1.
2.
3.
4.
5.
2.4
Detection ranges per detector / flame
simulator
Table 2-2:
Model
FS-UVIR-975
FS-IR-975
FS-HR-975
12
Verify that you are using the correct simulator that fits the tested detector per the
following table:
Table 2-1:
Flame Simulator compatibility
Simulator
FS-UVIR-975 FS-IR-975FS-HR-975
Verify that you are at the correct distance from the detector according to the type of
detector (see
Table
2-2) and the detector sensitivity.
Aim the Flame Simulator using the mechanical sight attowards the center of the
detector. Activate the button and adjust the spot to the center of the detector.Push
the Activate button and then use the laser spot for fine adjustment towards the
center of the detector.
Keep the simulator aimed at the detector for up to fifty seconds until you receive an
alarm.
Wait twenty seconds before repeating the test.

Detection ranges per detector / flame simulator

Detector types
975 UR
975 UF
975MR
975HR
Compatible with
975UF, 975UR 975MR975HR
Detector sensitivity
Testing distance
settings
50 ft. (15 m)
8 ft. (2.5 m)
60 ft. (20 m)
23 ft. (7 m)
50 ft. (15 m)
6.6 ft. (2 m)
100 ft. (30 m)
19.6 ft. (6 m)
150 ft. (45 m)
29.5 ft. (9 m)
200 ft. (60 m)
39.3 ft. (12 m)
50 ft. (15 m)
6.6 ft. (2 m)
100 ft. (30 m)
19.6 ft. (6 m)
150 ft. (45 m)
29.5 ft. (9 m)