3.1 Overview of connections
Connection number on
master
Power supply
134
135
136
USB 2.0
130
131
132
133
RS-232
105
106
107
108
109
111
112
RS-485
137
138
139
M-Bus Repeater Input
53
54
M-Bus Master Output
24
25
8
Designation
Colour/connector No.
N
Blue
L
Brown
PE
Yellow/green
VCC
Red/1
D-
White/2
D+
Green/3
GND
Black/4
RxD
2
TxD
3
GND
5
DTR
4
CTS
8
DSR
6
RTS
7
A/-
A+
GND
L1
L2
L1
L2
55121391_B1_GB_12.2013
Description
Neutral
Live
Protective earth
Max. recommended cable length: 5 m
5 V power supply
Data -
Data +
Ground
Max. recommended cable length: 15 m
Received Data
Transmitted Data
Ground
Data Terminal Ready
Clear To Send
Data Set Ready
Request To Send
Max. recommended cable length: 1,200 m
Transmit/Receive inverted
Transmit/Receive non-inverted
Ground
Jumper must be set to Repeater
M-Bus input to master in repeater mode
M-Bus input to master in repeater mode
4 sets connection terminals, connection in parallel
M-Bus output from master to meters
M-Bus output from master to meters
Need help?
Do you have a question about the M-Bus Master MultiPort 250L and is the answer not in the manual?
Questions and answers