Mitsubishi Electric PQHY-P72ZLMU-A Service Handbook page 226

2016
Table of Contents

Advertisement

[ VIII Test Run Mode ]
Model name of BC controller
Indoor temperature
Heat source water temperature
Heat source water flow rate
Indoor
Operating
unit
conditions
Pipe
length
Fan speed
Refrigerant charge
Current
Heat source
Voltage
unit
Compressor frequency
Indoor unit
BC controller (1/2/3)
LEV opening
LEV6
LEV7
High pressure (after O/S)/
Low pressure (before accumulator)
Pressure
switch
BC controller on the liquid side
(PS1)/Intermediate part (PS3)
Heat
source
unit
Sectional
temperatures
Indoor
unit
HWE15150
Item
DB/WB
°C [ °F]
m
[G/h]
[gpm]
No. of connected units
Unit
No. of units in operation
Model
Main pipe
Branch pipe
m [ft]
Total pipe length
[lbs-oz]
Pulse
MPa
[psi]
Discharge (TH4)
Heat exchanger outlet
Accumulator inlet
Accumulator outlet
°C [ °F]
Compressor inlet
Compressor shell bottom
LEV inlet
Heat exchanger outlet
Heat source unit model
PQRY-P168ZLMU-A
CMB-P108NU-GA1
26.7°C/19.4°C
[80 °F/67 °F]
29.4[85]
3
/h
7.20
[1902]
[31.7]
4
4
36/36/48/48
5 [16-3/8]
10 [32-3/4]
45 [148]
Hi
kg
19.1 [43]
A
13.4
V
575
Hz
97
325/325/387/387
2000/2000/210
41
3000
2.48/0.81
[360/117]
2.38/2.38
[345/345]
65 [149]
38 [100]
8 [46]
8 [46]
19 [66]
42 [108]
19 [66]
6 [43]
- 217 -
PQRY-P192ZLMU-A
CMB-P108NU-GA1
26.7°C/19.4°C
[80 °F/67 °F]
29.4[85]
7.20
[1902]
[31.7]
4
4
48/48/48/48
5 [16-3/8]
10 [32-3/4]
45 [148]
Hi
20.6 [46]
16.7
575
112
387/387/387/387
2000/2000/220
41
3000
2.56/0.81
[371/117]
2.46/2.46
[357/357]
65 [149]
39 [102]
8 [46]
8 [46]
19 [66]
42 [108]
19 [66]
6 [43]