Installation and Operation Instructions
Please read all instructional literature carefully and thoroughly before starting.
GENERAL
MISUSE OF THIS PRODUCT MAY CAUSE EXPLOSION
AND PERSONAL INJURY. THESE INSTRUCTIONS MUST
BE THOROUGHLY READ AND UNDERSTOOD BEFORE
DEVICE IS INSTALLED.
Cert number
20160531-E43374
Applicable Area
North America
Class I, Groups B, C and D; Class II,
Markings
Groups E, F and G; Class III
UL 1203;
Applicable Standards
CAN/CSA C22.2 No. 25
CAN/CSA C22.2 No. 30
Cert number
DEMKO 09 ATEX 0815573X
Applicable Area
Europe (EU)
II 2 G Ex db IIC T6 Gb; II 2 D Ex tb IIIC
Markings
T85°C Db IP66
Applicable Standards
EN IEC 60079-0; EN 60079-1; EN 60079-31
Cert number
IECEx UL 03.0001X
Applicable Area
International
Ex db IIC T6 Gb
Markings
Ex tb IIIC T85°C Db IP66
-40°C to +75°C
Applicable Standards
IEC 60079-0; IEC 60079-1; IEC 60079-31
Cert number
DEMKO 11 ATEX 1105261X
Applicable Area
Europe (EU)
Markings
II 1 G Ex ia IIC T6 Ga
Applicable Standards
EN IEC 60079-0; EN 60079-11
Cert number
IECEx UL 14.0075X
Applicable Area
International
Ex ia IIC T6 Ga
Markings
-50°C ≤ Tamb ≤ +60°C
Applicable Standards
IEC 60079-0; IEC 60079-11
120 SERIES FOR USE IN CLASS I, DIV. 1, GROUPS B, C & D;
CLASS II, DIV. 1, GROUPS E, F & G; CLASS III HAZARDOUS
LOCATIONS. ENCLOSURE TYPE 4X, IP66. AMBIENT
TEMPERATURE RANGE -50°C (-58°F) TO 71°C (160°F).
TO PREVENT IGNITION OF HAZARDOUS
ATMOSPHERES, DISCONNECT SUPPLY CIRCUITS
BEFORE OPENING. KEEP COVER TIGHT WHILE
CIRCUITS ARE ENERGIZED.
120 Series
Explosion-Proof Temperature and Indicating Temperature Switches
and Controls
Local Mount Types B121, B122, C120
Remote Mount Types E121, E122, F120; 820E, 822E
Refer to the final page for the Warranty.
ATEX AND IEC SPECIFIC CONDITIONS OF USE:
DIMENSIONS OF THE FLAMEPROOF JOINTS ARE
OTHER THAN THE RELEVANT MINIMUM OR MAXIMUM
SPECIFIED IN TABLES 1 THROUGH 2 OF EN 60079-1/IEC
60079-1. TEMPERATURE OPERATED SWITCHES ARE TO
BE MARKED WITH AN "X" AND THE DIMENSIONS OF THE
FLAMEPROOF JOINTS ARE AS FOLLOWS:
120's
Activation Plunger to adjustment screw hole
gap joints: 1.140 in/28.96 mm min length by
0.0039 in/0.099 mm max annular gap
Plunger Guide to enclosure through threaded
joints: minimum 8 ½ fully engaged threads
Cover to enclosure through threaded joints:
minimum 7 ½ fully engaged threads
121's & 122's
Activation Plunger to enclosure through hole
gap joints: 1.00 in/25.40 mm min length by
0.0030 in/0.076 mm max annular gap
Adjustment shaft to shaft through hole gap
joints: 1.050 in/26.67 mm min. length by 0.0035
in/0.089 mm max. annular gap
Cover to enclosure through threaded joints:
minimum 7 ½ fully engaged threads
ATEX AND IEC SPECIFIC CONDITIONS OF USE:
ENCLOSURE CONTAINS ALUMINUM. CARE MUST BE
TAKEN TO AVOID IGNITION HAZARD DUE TO IMPACT
OR FRICTION.
MAX. TEMPERATURE* LIMITS LISTED ON NAMEPLATE
MUST NEVER BE EXCEEDED, EVEN BY SURGES IN THE
SYSTEM. OCCASIONAL OPERATION OF UNIT UP TO
MAX. TEMPERATURE IS ACCEPTABLE, E.G., START-UP
AND TESTING. EXCESSIVE CYCLING AT MAXIMUM
TEMPERATURE LIMIT COULD REDUCE SENSOR LIFE.
CONTINUOUS OPERATION SHOULD NOT EXCEED THE
DESIGNATED ADJUSTABLE TEMPERATURE RANGE.
* Maximum Temperature - the highest temperature to which a
sensing element may be occasionally operated without adversely
aff ecting set point calibration and repeatability.
THIS PRODUCT DOES NOT HAVE ANY FIELD
REPLACEABLE PARTS. ANY SUBSTITUTION OF
COMPONENTS WILL INVALIDATE THIRD-PARTY ISSUED
APPROVALS AND CERTIFICATIONS, AND MAY IMPAIR
SUITABILITY FOR CLASS I, DIVISION 1 LOCATION.
1
IMT120 15

Advertisement

loading

Summary of Contents for United Electric Controls 120 Series

  • Page 1 IEC 60079-0; IEC 60079-11 DESIGNATED ADJUSTABLE TEMPERATURE RANGE. 120 SERIES FOR USE IN CLASS I, DIV. 1, GROUPS B, C & D; * Maximum Temperature - the highest temperature to which a CLASS II, DIV. 1, GROUPS E, F & G; CLASS III HAZARDOUS sensing element may be occasionally operated without adversely LOCATIONS.
  • Page 2 NECESSARY. surface mounted via the four 1/4” screw holes on the enclosure or mounting bracket. The 120 Series temperature switch utilizes either a liquid filled sensing stem (immersion stem, direct Type 820E and 822E mounting) or liquid filled sensing bulb (bulb &...
  • Page 3 Type 822E TO PREVENT IGNITION OF HAZARDOUS ATMOSPHERES, SEAL CONDUIT RUNS WITHIN 18” OF ENCLOSURE. N.O. N.C. COM. N.O. N.C. COM. ENSURE ELECTRICAL CONDUIT ENTRIES ARE PROPERLY SEALED TO PREVENT MOISTURE ENTRY. ❶ CALIBRATING Remove cover and wire device (See Figure 2). SCREW 3/16 VLT RED ❷...
  • Page 4 Type 820E NOTE: To adjust the Indicating Pointer (820E, 822E): To adjust the switch: ❶ ❶ Use an accurate test thermometer such as a thermocouple Remove the set point adjustment knob and clear cover with its probe mounted directly to the center of the sensing bulb. from the indicating enclosure (square) to access the pointer mechanism for adjustment.
  • Page 5: Recommended Practices

    Recommended Practices Model Number Range Cap Length / Division -180 to 120°F 2 ft -125 to 350°F 1 1/2 ft • A redundant device is necessary for applications -125 to 500°F 1 ft where damage to the primary device could -40 to 120°F 4 ft endanger life, limb or property.
  • Page 6 Type 822E dual switch 4 1/16 (177.8 mm) (119.3 mm) 6 3/8 1 1/16 GROUND (43.2 mm) (161.9 mm) SCREW 3 3/16 (81.0 mm) 1 3/16 2 1/4 5/64 (2 mm) (30.2 mm) (57.5 mm) SOCKET COVER- LOCK SCREW (22.2 mm) ADJUSTMENT “D”...
  • Page 7 French Warnings Translations Page Warning Text Texte d’Avertissement MISUSE OF THIS PRODUCT MAY CAUSE EXPLOSION AND PERSONAL Une mauvaise utilisation de cet appareil peut provoquer une INJURY. THESE INSTRUCTIONS MUST BE THOROUGHLY READ AND explosion et/ou des blessures corporelles. Ces consignes doivent être lues UNDERSTOOD BEFORE UNIT IS INSTALLED.
  • Page 8: Limited Warranty

    LIMITED WARRANTY LIMITATION OF SELLER’S LIABILITY Seller’s liability to Buyer for any loss or claim, including liability Seller warrants that the device hereby purchased is, upon incurred in connection with (i) breach of any warranty delivery, free from defects in material and workmanship and whatsoever, expressed or implied, (ii) a breach of contract, (iii) that any such device which is found to be defective in such a negligent act or acts (or negligent failure to act) committed...

This manual is also suitable for:

B121B122C120E121E122F120 ... Show all