Specifications; Fire Detection; Video Functionality; Electrical Specifications - FGD FlameSpec IR3 HD User Manual

Table of Contents

Advertisement

FlameSpec IR3 HD User Manual
9 Specifica ons
Fire Detec on
Detec on me and distance:
o 40ms - for fast fire burst or explosion
o 1.5s - for 1
o 4s - for 1
Field of view: 90° Horizontal, 75° Ver cal
Time Delay: 0-30 seconds (adjustable)
Built-in test: Automa c and Manual
Video Func onality
HD Video allowing clear imaging of fire and people at 100 . (30m) distance.
Video recording of alarm events 1 minute before and up to 3 minutes a er the flame is detected.
System integra on protocol: ONVIF (Open Network Video Interface Forum) Profile S
Electrical Specifica ons
Opera ng Voltage: 24 VDC nominal (18-32 VDC)
Current Consump on:
o Standby
o Maximum
Cable Entries: 2x conduit entries 3/4" NPT or M25, with one entry plugged with a suitably
cer fied stopper.
Wiring: 14-17AWG (2.5-1.0mm
For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com
2
(0.1m
2
) N-heptane pan fire at 100
2
(0.1m
2
) N-heptane pan fire at 230
180mA
300mA all systems in opera on (including window heater)
2
)
F101V0020.08
(30m)
(70m)
31