5 Maintenance

A er powering up, the detector should work maintenance free. Regular checks should be in the form of
a physical inspec on and to periodically ensure the op cal surfaces are clean (windows and reflec ve
mirror). It is also recommended to perform a func on test annually or in line with local requirements,
whichever is the sooner.
Warning
The sensor module in the front half of the detector contains no serviceable components and should
never be opened. The terminal compartment at the back is the only part of the housing that should be
opened by the user. Any viola on of these instruc ons will invalidate the warranty.

Cleaning Procedure

To clean the detector:
a) Disconnect the power to the unit and disable/inhibit any ex nguishing equipment that is
connected to the unit.
b) Use water and detergent to clean the detector windows and underside of the reflector. Rinse
with a so cloth, co on swab, or ssue.
c) Where dust, dirt or moisture accumulates on the window, first clean the window with a so
op cal cloth and detergent, and then rinse with a clean so cloth, co on swab, or ssue. If
contamina on con nues to be an issue consider using the air shield.