Specifications; Fire Detection; Electrical Specifications - FGD FlameSpec IR3-H2 User Manual

Hide thumbs Also See for FlameSpec IR3-H2:
Table of Contents

Advertisement

FlameSpec IR3-H2 User Manual

9 Specifications

Fire Detection

Detection time and distance:
o 40ms - for fast fire burst or explosion
o 1.5s - for 32" (0.8m) hydrogen fire at 0–66ft. (0–20m)
o 4s - for 32" (0.8m) hydrogen fire at 66–100ft. (20–30m)
Field of view: 90° Horizontal, 75° Vertical
Time Delay: 0-30 seconds (adjustable)
Built-in test: Automatic and Manual

Electrical Specifications

Operating Voltage: 24 VDC nominal (18-32 VDC)
Current Consumption:
o Standby
o Maximum
Cable Entries: 2x conduit entries 3/4" NPT or M25, with one entry plugged with a suitably
certified stopper.
Wiring: 14 to 17 AWG (2.5mm
For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com
F150V0020.09
120mA
180mA all systems in operation (including window heater)
2
to 1.0mm
2
)
30