10 Performance; Fls-Ir3-Hd-Asx1, Fls-Ir3-Hd-Asx2 (Standard Model) - FGD FlameSpec IR3 HD User Manual

Table of Contents

Advertisement

FlameSpec IR3 HD User Manual

10 Performance

The following tables show test results of detec on distances and mes for different fire scenarios. Each
table lists results for a different sensi vity se ng. For liquid fires the size of fire refers to the size of the
pan, filled with the fuel. For gas fires the length of the plume is

FLS-IR3-HD-ASX1, FLS-IR3-HD-ASX2 (Standard model)

Extreme Sensitivity
Fuel
N-Heptane
N-Heptane
N-Heptane
Gasoline
Gasoline
Methane
LPG
Diesel
JP5
JP5
Kerosene
Methanol
Ethanol
Isopropanol
Polypropylene
Paper
Syngas
Wood
High Sensitivity
Fuel
N-Heptane
LPG
JP5
Methanol
For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com
Pan Size
Distance ft (m)
1 x 1 ft
1 x 1 ft
1 x 1 ft
1 x 1 ft
2 x 2 ft
32" plume
32" plume
1 x 1 ft
1 x 1 ft
2 x 2 ft
1 x 1 ft
1 x 1 ft
1 x 1 ft
1 x 1 ft
1 x 1 ft
1 x 1 ft
32-in Plume
1 x 1 ft
Pan Size
Distance ft (m)
1 x 1 ft
32" plume
1 x 1 ft
1 x 1 ft
F101V0020.08
listed.
Average Response
262 (80)
230 (70)
98 (30)
230 (70)
328 (100)
148 (45)
180 (55)
164 (50)
164 (50)
295 (90)
164 (50)
131 (40)
125 (38)
180 (55)
115 (35)
79 (24)
98 (30)
148 (45)
Average Response
Time (Seconds)
197 (60)
148 (45)
148 (45)
125 (38)
Time (Seconds)
9.0
4.1
1.5
3.6
5.3
3.3
4.8
2.9
5.8
9.2
4.1
4.1
4.2
3.5
10.1
0.9
3.3
3.8
3.2
2.9
4.9
5.5
37