LG MULTI F LMU183HV Installation Manual page 119

Table of Contents

Advertisement

Installation
Connecting the piping to the indoor unit
and drain hose to drain pipe.
1. Align the center of the pipes and suffi-
ciently tighten the flare nut by hand.
2. Tighten the flare nut with a wrench.
Outside diameter
mm
inch
Ø6.35
1/4
Ø9.52
3/8
Ø12.7
1/2
Ø15.88
5/8
Ø19.05
3/4
3. Next, extend the indoor unit's drain hose.
Then attach the drain pipe.
Installation Information. For left piping. Follow the instruction below.
Good case
• Press on the upper side of clamp and unfold the tubing to slowly downward.
Bad case
• Bending the pipe from right to left may cause damage to the tubing.
16 Multi Air Conditioner
Torque
N. m
kgf.m
lbf.ft
14~18
1.4~1.8
10~13
34~42
3.5~4.3
25~31
49~61
5.0~6.2
36~45
69~82
7.0~8.4
51~60
100~120 10.0~12.2 73~88
Indoor unit tubing
Flare nut
Wrench
Indoor unit tubing
Drain pipe
Adhesive
Pipes
Open-end wrench (fixed)
Flare nut
Connection pipe
Indoor unit drain hose
Vinyl tape(narrow)

Advertisement

Table of Contents
loading

Table of Contents