Specifications
Electrostatic Discharge
ESD:
RFI and Interference Tests
1 MHz Burst
Disturbance:
Radiated EMI:
Fast Transient
Disturbance:
Surge Immunity:
Conducted RF
Immunity:
Flicker:
Showering Arc:
© 2003–2008. All rights reserved.
All trademarks are the property of their respective
holders. Products appearing in this document may be
covered by US and Foreign patents. The information in
this document is provided for informational use only
and is subject to change without notice.
825-PR12D RTD Scanner
EN 61000-4-2
15 kV air, 8 kV contact
IEC 60255-22-1
2500 V peak common
and differential mode
EN 61000-4-3
10 V/m
IEEE C37.90.2
10 V/m
EN 61000-4-4
Level 4
4 kV, 2.5 kHz at power
supply port
2 kV, 5 kHz at RTD and
functional earth port
IEEE C37.90.1-1989
3000 V oscillatory
5000 V transient
EN 61000-4-5
500 V, 1000 V
line-to-line
500 V, 1000 V, 2000 V
line-to-earth (applied
to power supply input
port)
EN 61000-4-6
10 Vrms
IEC 61000-3-3
Part 3-3–equipment
with <16 A per phase
NEMA ICS1-2000
Vibration and Shock Tests
Shock and Bump: EN 60068-2-27
Sinusoidal
EN 60068-2-6
Vibration:
Seismic:
IEC 60255-21-3
Certifications
ISO: Device is designed and manufactured to
an ISO 9001 certified quality program.
UL: UL Listed to the requirements of UL 508
Industrial Control Equipment.
CSA: CSA C22.2 No. 14 for Industrial
Control Equipment.
CE: Certified to EN 50263 and EN 60947-4-1
1999 (EMC), and 60947-4-1 (LVD).
Hazardous Locations: Class I, Division 2,
Groups A, B, C, and D; Temp. Code T4A;
CSA C22.2 No. 213-M, 1987 (1999)
*PM1553-01*
Class 1–Shock
withstand and bump
(5G)
Class 2–Shock response
(30G)
Class 1–Endurance (1G)
Class 2–Response (2G)
Class 2
Date Code 20080722

Advertisement