Carrier 59TP6C Installation, Start-Up, Operating And Service And Maintenance Instructions page 48

Two-stage, non-communicating, variable 25-speed, ecm multipoise, condensing gas furnace with intelisense
Table of Contents

Advertisement

59TP6C: Installation, Start-up, Operating and Service and Maintenance Instructions
Venting System Length Calculations
The Total Equivalent Vent Length (TEVL) for EACH combustion air or vent pipe equals the length of the venting system, plus the equivalent length of
elbows used in the venting system from
Standard vent terminations or factory accessory concentric vent terminations count for zero deduction.
See vent system manufacturer's data for equivalent lengths of flexible vent pipe or other termination systems. DO NOT ASSUME that one foot of
flexible vent pipe equals one foot of straight PVC/ABS DWV vent pipe.
Compare the Total Equivalent Vent Length to the Maximum Equivalent Vent Lengths in
Example 1
A direct-vent 60,000 BTUh furnace installed at 2100 ft. (640M). Venting system includes FOR EACH PIPE:
70 feet (22 M) of vent pipe, 65 feet (20 M) of combustion air inlet pipe, (3) 90º long-radius elbows, (2) 45º long-radius elbows, and a factory accessory
concentric vent kit.
Can this application use 2" (50 mm ND) PVC/ABS DWV vent piping?
Measure the required linear length of air inlet and vent pipe; insert the longest of
the two here
Add equiv length of (3) 90º long-radius elbows
(use the highest number of elbows for either the vent or
inlet pipe)
Add equiv length of (2) 45º long-radius elbows
(use the highest number of elbows for either the vent or
inlet pipe)
Add equiv length of factory concentric vent term
Add correction for flexible vent pipe, if any
Total Equivalent Vent Length (TEVL)
Maximum Equivalent Vent Length (MEVL)
Is TEVL less than MEVL?
Example 2
A direct-vent 60,000 BTUh furnace installed at 2100 ft. (640M). Venting system includes FOR EACH PIPE:
100 feet (30 M) of vent pipe, 95 feet (29 M) of combustion air inlet pipe, (3) 90º long-radius elbows, and a polypropylene concentric vent kit. Also
includes 20 feet (6.1 M) of flexible polypropylene vent pipe, included within the 100 feet (30 M) of vent pipe.
VERIFY FROM POLYPROPYLENE VENT MANUFACTURER'S INSTRUCTIONS for the multiplier correction for flexible vent pipe.
Can this application use 60mm o.d. (2") polypropylene vent piping? If not, what size piping can be used?
Measure the required linear length of RIGID air inlet and vent pipe; insert the longest of
the two here: 100 ft. Of rigid pipe - 20 ft. Of flexible pipe
Add equiv length of (3) 90º long-radius elbows (use the
highest number of elbows for either the vent or inlet pipe)
Add equiv length of 45º long-radius elbows
(use the highest number of elbows for either the vent or
inlet pipe)
Add equiv length of factory concentric vent term
Add correction for flexible vent pipe, if any
* VERIFY FROM VENT MANUFACTURER'S INSTRUCTIONS; For example only, assume 1 meter of
flexible 60mm (2") or 80mm (3") polypropylene pipe equals 2.0 meters (6.5 ft.) of PVC/ABS pipe.
Total Equivalent Vent Length (TEVL)
Maximum Equivalent Vent Length (MEVL)
Is TEVL less than MEVL?
Maximum Equivalent Vent Length (MEVL)
Is TEVL less than MEVL?
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Table
16.
3
x
2
x
3
0
9
2*
Table
15.
70 ft.
Use length of the longer of the vent
=
(22 M)
or air inlet piping system
3 ft.
9 ft.
=
From
(0.9 M)
(2.7 M)
1.5 ft.
3 ft.
=
From
(0.5 M)
(0.9 M)
0 ft.
From
From Vent Manufacturer's
0 ft.
instructions; zero for PVC/ABS DWV
82 ft.
Add all of the above lines
(25 M)
95 ft.
For 2" pipe from
(29 M)
YES
Therefore, 2" pipe MAY be used
80 ft.
=
(24 M)
5 ft.
15 ft.
x
=
(1.5 M)
(4.6 M)
0 ft.
x
=
(0 M)
3.3 ft
30 ft.
x
=
(0.9 M)
(9 M)
20 ft.
40 ft.
x
=
(6.1 M)
(12.2 M)
165 ft.
(50 M)
95 ft.
(29 M)
NO
185 ft.
(57 M)
YES
48
Table 16
Table 16
Table 16
Table 15
Use length of the longer of the vent
or air inlet piping system
Example from polypropylene vent
manufacturer's instructions, Verify from vent
manufacturer's instructions.
Add all of the above lines
For 2" pipe from
Table 15
Therefore, 60mm (2") pipe may NOT be
used; try 80mm (3")
For 3" pipe from
Table 15
Therefore, 80mm (3") pipe MAY be used