Panasonic U-8MF3R7 Installation Instructions Manual page 45

Hide thumbs Also See for U-8MF3R7:
Table of Contents

Advertisement

o38.1
100
90
80
70
60
50
40
10
20
30
Ambient temperature [°C]
If the exterior of the outdoor unit
valves has been finished with a
square duct covering, make sure
CAUTION
you allow sufficient space to use the
valves and to allow the panels to be
attached and removed.
Taping the flare nuts
Wind the white insulation tape around the flare nuts at the gas
tube connections. Then cover up the tubing connections with
the flare insulator, and fill the gap at the union with the supplied
black insulation tape. Finally, fasten the insulator at both ends
with the supplied vinyl clamps.
Sealer
Unit side
insulator
Flare nut
Drain pipe and insulator
Drain insulator
and clamp
Packing clamp
Small hose band
Never grasp the drain or refrigerant connecting outlets
when moving the unit.
o41.28
100
90
Thickness
80
30mm
Thickness
70
20mm
60
Thickness
50
10mm
40
40
50
10
Ambient temperature [°C]
Insulation tape (white)
Flare insulator
Tube insulator
Vinyl clamps
Refrigerant tubing and insulator
Insulation
tape
Vinyl
clamp
Flare
insulator
Seal
The procedure used for
installing the insulator
for both gas and liquid
tubes is the same.
Thickness
30mm
Thickness
20mm
Thickness
10mm
20
30
40
50
Insulation material
The material used for insulation must have good insulation
characteristics, be easy to use, be age resistant, and must not
easily absorb moisture.
Be sure to use the heat-resistant insulator corresponding to the
gas tube of 120 °C or above and other tubes of 80 °C or above.
CAUTION
45
After a tube has been insulated, never
try to bend it into a narrow curve
because it can cause the tube to
break or crack.