Installing/mounting
4.4 Measurement setup - Flow
Flow formula:
If the flow formula of your flume is known, you should select this option, as the
accuracy of the flow measurement is highest here.
Manufacturer definition:
If you use a Parshall flume from the manufacturer ISCO, this option must be selected.
This gives you a high accuracy of flow measurement with easy configuration.
Alternatively, you can also take over Q/h table values provided by the manufacturer
here.
Note
Detailed project planning data can be found at the channel manufacturers and in the
technical literature.
The following examples serve as an overview for flow measurement.
Rectangular overfall
1
2
3
4
Figure 4.9
16
Flow formula: Q = k x h
ISCO-Parshall-Flume
Q/h table (assignment of height with corresponding flow in a table)
Overfall orifice (side view)
Upstream water
Tailwater
Overfall orifice (view from tailwater)
Flow measurement with rectangular flume: h
flume
exp
= max. filling of the rectangular
max.
Operating Instructions, 10/2022, 62709-76-01, A5E49829030