A5 Technical Description; Technical Data: Circuit Breaker Type Gl 310-Gl 312 - GE GL 310 F3/4031 P/VR Operating Instructions Manual

High voltage circuit breaker
Table of Contents

Advertisement

A5
Technical Description
A5.1

Technical Data: Circuit Breaker Type GL 310-GL 312

Type
Rated voltage
Rated normal current
Rated frequency
Rated power-frequency withstand voltage
50 Hz, 1 min
- To ground
- Across open switching device
Rated lightning impulse withstand voltage
- To ground
- Across open switching device
Rated switching impulse withstand voltage
(Vn > 245 kV)
- To ground
- Across open switching device
Rated short-circuit breaking current
- R.m.s. value of the a.c. component
of current
- Percentage of d.c. component
Minimum opening time
First-pole-to-clear factor
Transient recovery voltage
- Peak value
- Rate of rise
Short-line fault
- Surge impedance
- Peak factor
Rated short-circuit making current
Rated out-of-phase breaking current
Rated duration of short circuit
Rated operating sequence
Rated line-charging breaking current
Rated cable-charging breaking current
SF
weight per breaker -30°C / -40°C
6
(porcelain insulator)
SF
weight per breaker -30°C / -40°C
6
(composite insulator)
*60 Hz only for -30°C
REV6
/REV3
GL 310
F3/4031 P/VR
kV
A
Hz
50 / 60*
kV
kV
kV
kV
kV
kV
kA
%
ms
1.3 / 1.5
kV
kV/µs
kA
kA
s
A
A
kg
8.3 / 7.8
kg
13.0 / 9.6
OI 248 (EN)
T
D
ECHNICAL
ESCRIPTION
GL 311
F3/4031 P/VR
100
123
3150
3150
50 / 60*
185
230
185
230
450
550
450
550
not applicable
not applicable
40
40
45
45
26
26
1.3 / 1.5
171
211
2.0
2.0
450
450
1.6
1.6
104
104
10
10
3
3
O-0.3s-CO-3min-CO
or CO-15s-CO
20
31.5
125
140
8.3 / 7.8
13.0 / 9.6
GL 312
F3/4031 P/VR
145
3150
50 / 60*
275
275
650
650
40
45
26
1.3 / 1.5
249
2.0
450
1.6
104
10
3
50
160
8.3 / 7.8
13.0 / 9.6
123

Advertisement