Download Print this page

Viking VCCC115-SS81A User Manual & Service Manual page 40

Advertisement

USER GUIDE
SERVICE MODE GUIDE
(For adjustments, see Service Mode Guide)
0. Exit
1. Thermistor 1 temperature not including offsets.
2. Thermistor 2 temperature not including offsets.
3. Thermistor 3 temperature not including offsets.
4. Thermistor 4 temperature not including offsets.
5. Thermistor 1 offset. (+/- 10)
6. Thermistor 2 offset. (+/- 10)
7. Thermistor 3 offset. (+/- 10)
8. Thermistor 4 offset. (+/- 10)
9. Thermistor 2 set point
10. Thermistor 3 set point.
11. Thermistor 4 set point.
12. Defrost Interval (0 to 99 hr)
13. Defrost duration (0 to 99 min)
14. Error Log (See Appendix)
15. Clear error log (hold light key until cleared)
16. Thermistor 1 differential (+5)
17. Thermistor 3 differential (+5)
18. Evaporator fan on delay (0 to 99 sec)
19. Evaporator fan off delay (0 to 99 sec)
20. Individual component toggle
- Option #0 – Exit
- Option #1 – Relay 1
- Option #2 – Relay 2
- Option #3 – Relay 3
- Option #4 – Relay 4
- Option #5 – Relay 5
- Option #6 – Relay 6
- Option #7 – DC Output 1
- Option #8 – DC Output 2
- Option #9 – DC Output 3
- Option #10 – DC Output 4
- Option #11 – DC Output 5
- Option #12 – Serial output (Compressor)
21. Model number
22. Light All Segments
23. Activate Defrost/Harvest- press and hold for 3 seconds
to activate defrost/harvest
24. Defaults- press and hold for 3 seconds to restore all
values to factory defaults.
25. Main Software (Display only)
26. Live Log Period (frequency that data is output to
diagnostics port)
27. Factory test mode (0=Off, 1=On)
28. Compressor RPM
29. Freeze time adjust (Model 54 only)
30. Harvest time adjust (Model 54 only)
31. Low temp alarm limit (Model 55 only)
32. High temp alarm limit (Model 55 only)
Control Operation-Service
APPENDIX
SERVICE MODE GUIDE
THERMISTOR 1
1.
This shows the pure thermistor reading with no offsets
taken into account.
THERMISTOR 2
2.
This shows the pure thermistor reading with no offsets
taken into account.
3.
Does not apply to this model.
4.
Does not apply to this model.
5.
THERMISTOR 1 OFFSET
(DO NOT MAKE AN ADJUSTMENT TO THIS WITHOUT
CONTACTING TECH LINE: +1 414.354.0300)
This calibration is only to be used if actual temperature
at thermistor #1 is off from set point.
By adjusting the offset higher we can force the unit
to drive the temperature down below the set point.
(example: adjusting from 0 to +2 will drop the unit
temperature 2 degrees)
6.
THERMISTOR 2 OFFSET
(DO NOT MAKE AN ADJUSTMENT TO THIS WITHOUT
CONTACTING TECH LINE: +1 414.354.0300)
7.
Does not apply to this model.
8.
Does not apply to this model.
9.
Does not apply to this model.
This shows the thermistor reading with offsets taken
into account.
10. Does not apply to this model.
11. Does not apply to this model.
12. Does not apply to this model.
13. Does not apply to this model.
14. VIEW ERROR LOG
A list of errors in the order they occurred will scroll on
the display. All errors are logged in memory. Only door
error is displayed on the display and has an audible
signal.
E0: Door 1 open.
E1: Thermistor 1 open.
E2: Thermistor 2 open.
E3: Does not apply to this model.
E4: Does not apply to this model.
E5: Thermistor 1 shorted.
E6: Thermistor 2 shorted.
E7: Does not apply to this model.
E8: Does not apply to this model.
E9: Door open.
E10: Door 2 open.
40

Advertisement

loading